![CommScope SYSTIMAX EHD User Manual Download Page 5](http://html1.mh-extra.com/html/commscope/systimax-ehd/systimax-ehd_user-manual_2643801005.webp)
TECP-91-005 • Issue 5 • October 2017
Page 5
© 2017
CommScope
. All Rights Reserved.
1.3
Specifications
lists specifications for the SYSTIMAX EHD Panel.
supported adapter packs and modules for the SYSTIMAX EHD Panel.
2
UNPACKING AND INSPECTION
1. Inspect the exterior of the shipping container(s) for evidence of rough handling
that may have damaged the components in the container.
2. Unpack each container while carefully checking the contents for damage and
verify with the packing slip.
3. If damage is found or parts are missing, file a claim with the commercial carrier
and notify CommScope Customer Service. Save the damaged cartons for
inspection by the carrier.
4. Refer to
if you need to contact CommScope.
5. Save shipping containers for use if equipment requires shipment at a future date.
3
UNPACKING A PANEL WITH A PRETERMINATED CABLE
The pre-terminated panel is shipped with the panel mounted on top of a spool
containing the cable. The stub end of the cable is unwound to a splice vault or other
point of termination. To protect the panel and cable windings contained within the
upper cylinder of the shipping unit, It is critical to leave the foam packaging material
surrounding the panel in place until the unit has been transported to the final
installation location. Transporting the unit without the foam packaging in place may
result in damage to the panel and/or cable. To unpack and mount a fully loaded panel,
use the following procedure.
Table 1. SYSTIMAX EHD Panel Specifications
PARAMETER
SPECIFICATION
REMARKS
Operating conditions
14
F to +140
F (
10
C to +60C)
Humidity
10% to 95% RH
No condensation
Storage conditions
40
F to +158
F (
40
C to
+70
C)
Dimensions (2RU) D x W x H
(with mounting brackets)
19.64 in. (49.9 cm) D x 19.09 in.
(48.5 cm) W x 3.5 in. (6.04 cm) H
Width without mounting brack-
ets: 17.27 in. (43.9 cm)
Weight per 2RU
23.4 lbs. (1.06 Kg)
Table 2. SYSTIMAX EHD Panel Supported Adapter Packs and Modules
DESCRIPTION
FRONT
CONNECTOR
TYPE
FRONT
PORT
COUNT
REAR CONNECTOR
TYPE
REAR
PORT
COUNT
FIBER
CONFIGURATION
LC Adapter Pack
LC
24
LC
24
NA