3. Commissioning
Page 36
MF0150A4A.doc Manual for ION-M7P/17EHP/19P
The Mains cable is part of the delivery. It’s available in two wiring configurations:
Prot ect ive Cap
Wiring 1
Pin Name Color
1 Phase Black
2 Neutral White
3 n.c. n.c
PE Ground Green
Wiring 2
Pin Name
Color
1 Phase
Brown
2 Neutral
Blue
3 n.c.
n.c
PE Ground
Green/Yellow
table 3-2 AC power cable pinning
For the AC power supply connection, a minimum cross section of 1.5
mm
2
is required. Each wire must observe the applicable national
regulations regarding loop impedance, voltage drop, and methods of
installation. Make sure to connect the correct voltage to the unit.
Note:
Do not connect or disconnect the power cord at the mains connector while
power is on. Turn off mains* power before connecting the power cord at
the Remote Unit, then, engage mains again.
* Mains power must be interrupted with an external mains breaker. For the mains breaker, observe
the following recommendation:
120 Volt / 20 Amp max. or 240 Volt / 16 Amp, single-phase, 50 / 60 Hz AC service is needed, i.e. the
external AC breaker should be 20 Amps max. for 120-Volt service or 13 - 16 Amps for 240-Volt
service.