1.0 Introduction
CommFront User Manual
4
1.2 Factory Settings
IP Settings:
Static IP
IP Address:
192.168.1.200
Subnet Mask:
255.255.255.0
Gateway:
192.168.1.254
DNS:
8.8.8.8
COM Port Settings:
115.2Kbps, 8, N, 1
Local Port:
502
Remote IP:
192.168.1.211
Remote Port:
20000
Modbus:
Modbus RTU <-> Modbus TCP (OFF)
User Name:
admin
Password:
superuser
Note: To restore factory settings, press the “reset” button for 5 to 15 seconds.
1.3 Hardware
1.3.1 Specifications
Compatibility:
EIA/TIA RS-232C; IEEE802.3
Power Source:
5 to 36 VDC
Power Consumption:
Less than 1W
Configuration:
AT commands (RS-232) or built-in web server
Ethernet Network:
10/100M Auto-Negotiation; MDI-X auto-crossover
Network Protocols:
IPv4; TCP/UDP/HTTP; ARP; ICMP
Network Buffer Size:
TX: 6KB; RX: 4KB
IP Settings:
Static IP or DHCP
Operating Modes:
TCP Server & Client; UDP Server & Client; Httpd
Client
Max. No. of Client Connections: 8
Serial Port:
600 bps to 460 Kbps; RFC 2217 compliant
Serial Port Buffer Size:
RX: 2KB
Communication Protocols:
RS-232C; Modbus RTU; Modbus TCP
Protection:
Up to 15kV ESD; 600W Surge Protection
Distance (Ethernet):
328ft (100m)
Distance (RS-232):
16ft (5m)
Connectors (Ethernet):
1x RJ45
Connectors (RS-232):
1x 3-Way Terminal Block (TX, RX, GND)
Connectors (Power):
2-way terminal block
Dimensions (L x W x H):
4.3x1.1x2.6 in (110x28x65 mm)
Weight:
0.2 lb (90 g)
Operating Temperature:
-40ºF to 185ºF (-40ºC to 85ºC)
Operating Humidity:
5% to 95% Non-condensing