Introduction
Recommended Wire and Cables
For the full version of this manual, please visit COMMAX online
www.commax.com > Customer > Manual and download full manuals for installation and
users.
Access Control IDentry-C4 Installation Manual
http://www.commax.co.kr/boardnew/lib/downfile.php?db=TB_ENGLISH_manual&fnum=128
Access Control IDentry Access Control CAMS-C User Manual
http://www.commax.co.kr/boardnew/lib/downfile.php?db=TB_ENGLISH_manual&fnum=131
*CAMS-C Free version covers up to 8 controllers, please feel free to contact us
if you would like to purchase full version CAMS-C for more than
8 controllers.
Product
Quantity
Main
Board(FULL
PRODUCT)
1
*If C4 needs to be assembled, the product consists of 1 main board, 12 screws and 6
supporters
C4
CAMS-C(SOFTWARE)
SMART & EFFICIENT NETWORK ACCESS
CONTROLLER
ACCESS CONTROL MANAGEMENT SYSTEM
FLEXIBILITY AND COMPATIBILITY IN SYSTEM
INTEGRATION
•
Flexibility in System Integration
•
Organic expansion
•
Easy management
•
Modular based architecture
•
Compatibility with 3
rd
party systems
•
Integrated central monitoring
•
4 reader control
•
Unlimited controller integration
•
12 inputs & 8 outputs (up to 28 & 24)
•
Fast Ethernet & Weigand
•
Global Anti-passback
•
AES/3DES encrypted communication
•
Web server embedded
•
Auto detects card formats
•
Supports HID products
•
Unlimited Clients
•
Unlimited access rights
•
100,000 users
•
256/256 Time schedules/holidays
•
Supports FP/Iris biometric readers
•
AES/3DES encrypted communication
•
Time-attendance & Meal management
•
Reporting tool
•
Supports Multiple languages
NO.
Use
Recommended Cable
Distance
Limit
1
Power supply
IDentry-C4
Belden #9409, 18 AWG
2 conductor, unshielded
5m
2
Reader
IDentry-C4
Belden #9512, 22 AWG
4 conductor, unshielded
100m
3
Input Device
IDentry-C4
Belden #9512, 22 AWG
4 conductor, unshielded
100m
4
Output Device(Lock/alarm)
IDentry-
C4
Belden #9409, 18 AWG
2 conductor, unshielded
100m
5
Network
IDentry-C4
UTP Cable CAT5(Category5)
No.
Name
Description
①
Screw hole
4 screw holes to fix the ACU board to its case
②
Power input Port
DC +12V max 2A (excluded reader and lock/alarm device power
source)
③
Reply output Port
Output port for lock or alarm devices Form-C Type (NO, COM,
NC)
④
RJ45
Ethernet port for communication with PC and among controllers
⑤
Reader port
Wiegand format reader port
⑥
2 state input ports
Input ports with 2 state of ON/OFF
⑦
4 state supervised
input ports
8 inputs monitoring Open loop, Shorted loop, Grounded loop an
d Line fault
⑧
LED output port
Output port for LED displaying power/ACU status/communicatio
n status (output current : 50mA)
⑨
Initialization switc
h
Switch to initialize ID/EVENT/network configuration/ other config
uration
Cable Connection
IDentry-C4
Quick Manual
December 2015 Ver. 2