6
Touch the
UP/DOWN
keys to select 0,
1, 2.
Touch
NEXT
or
ENTER.
Option
NEXT
ENTER
Differential Mode0
Differential Mode1
Differential Mode2
o
0.5 On/Off Span.
o
1.0 On/Off Span.
o
1.5 On/Off Span.
Touch the
UP
key to select ON to turn
on smart recovery or touch the
DOWN
key to select OF to turn smart
recovery off.
Touch
NEXT
or
ENTER.
Smart recovery initiates a heating or cooling call so that the space is at temperature
when the setback period ends.
Option
NEXT
ENTER
Touch the
UP/DOWN
keys to select
the heating temperature when the
space is vacant.
Touch
NEXT
or
ENTER
.
Option
NEXT
ENTER
Touch the
keys to
select the cooling temperature
when the space is vacant.
Touch
or
UP/DOWN
NEXT
ENTER.
Option
NEXT
ENTER
Cool
Vacant
Vacant
Touch the
UP/DOWN
keys to change
the downstairs (Inside) temperature to
the temperature that the user feels is
correct.
Touch
NEXT
or
ENTER
.
Inside
Option
NEXT
ENTER
Heat
12 Vacant Cooling Setpoint
Range: 74 F to 95 F
o
o
Factory Default: 80 F.
o
11 Vacant Heating Setpoint
Range: 44 F to 75 F
o
o
Factory Default: 65 F.
o
09 Setting On-Off Temp Differential
Factory Default: #1. Range: 0, 1 or 2.
10 Smart Recovery
Factory Default: Off. Range: On or Off.
13 Calibrate Downstairs Temperature Sensor
Factory Default: None.
o
Range - +/-5
Touch the
UP/DOWN
keys to
change the upstairs (Inside2)
temperature to the temperature
that the user feels is correct.
Touch
NEXT
or
ENTER
Inside2
Option
NEXT
ENTER
Touch the
keys to
set the time in minutes to
update the upstairs and
downstairs airflow.
Touch
or
UP/DOWN
NEXT
ENTER.
Option
NEXT
ENTER
This is the frequency, in minutes, that the damper position is updated.
14 Calibrate Upstairs Temperature Sensor
Factory Default: None.
o
Range - +/-5
15 Airflow Update Time
Factory Default: 2 Minutes. Range: 1 to 20 Minutes.
Touch the
UP/DOWN
keys to change
the minimum off time (minutes) before
restarting the compressor.
Touch
NEXT
or
ENTER.
Option
NEXT
ENTER
Option
NEXT
ENTER
Touch the
UP/DOWN
keys to change
the minimum run time (minutes)
before turning a system off.
Touch
NEXT
or
ENTER
.
Option
NEXT
ENTER
Touch the
UP/DOWN
keys to change
the minimum off time (minutes) before
restarting a gas furnace or electric
strip heater.
Touch
NEXT
or
ENTER
.
06 Compressor Minimum Off Time
Factory Default: 2 Minutes. Range: 0 to 9 Minutes
07 Heating Minimum Off Time
Factory Default: 0 Minutes. Range: 0 to 9 Minutes
08 Minimum Run Time
Factory Default: 2 Minutes. Range: 0 to 9 Minutes
Option
NEXT
ENTER
Touch the
UP/DOWN
keys to set 0, 1
or 2 stage.
Touch
NEXT
or
ENTER
.
This option is used to set the number of heating stages.
Factory Default: 1 Stage. Range: 0,1 or 2
Option
NEXT
ENTER
Touch the
UP
key to select “EL” for
electric operation where the
thermostat activates the indoor fan (G
terminal) during heating calls or
DOWN
key to select GA for gas
operation where the equipment
plenum sensor activates the indoor
fan in heating calls.
05 Setting the Fan Operation
Factory Default: Gas. Range: GA or EL
(Only displayed
if GE selected)
Touch
NEXT
or
ENTER
.
04 Setting the Heating Stages