•
Use clean, dehydrated, sealed refrigeration grade tubing.
•
Always keep tubing sealed until tubing is in place and connections are to be
made.
•
Blow out the liquid and vapor lines with dry nitrogen before connecting to the
outdoor unit and indoor coil. Any debris in the line set will end up plugging the
expansion device.
•
As an added precaution, a high quality filter drier is standard on R-410A units.
•
Do not allow the vapor line and liquid line to be in contact with each other. This
causes an undesirable heat transfer resulting in capacity loss and increased
power consumption. The vapor line must be insulated.
•
If tubing has been cut, make sure ends are deburred while holding in a position
to prevent chips from falling into tubing. Burrs such as those caused by tubing
cutters can affect performance dramatically, particularly on small liquid line
sizes.
•
For best operation, keep tubing run as short as possible with a minimum num-
ber of elbows or bends.
•
Locations where the tubing will be exposed to mechanical damage should be
avoided. If it is necessary to use such locations, the copper tubing should be
housed to prevent damage.
•
If tubing is to be run underground, it must be run in a sealed watertight chase.
•
Use care in routing tubing and do not kink or twist. Use a good tubing bender
on the vapor line to prevent kinking.
•
Route the tubing using temporary hangers, then straighten the tubing and
install permanent hangers. Line must be adequately supported.
•
The vapor line must be insulated to prevent dripping (sweating) and prevent
performance losses. Armaflex and Rubatex are satisfactory insulations for this
purpose. Use 1/2” minimum insulation thickness, additional insulation may be
required for long runs.
•
Check Table 3 for the correct vapor line size. Check Table 4 for the correct liq-
uid line size.
7.5 Tubing Connections
Indoor coils have only a holding charge of dry nitrogen. Keep all tube ends sealed
until connections are to be made.
•
Use type “L” copper refrigeration tubing. Braze the connections with the follow-
ing alloys:
14
TABLE 6
SUCTION LINE SIZE – OUTDOOR UNIT BELOW INDOOR COIL – (-)PRL HEAT PUMPS
2-Stage
R-410A
System
Capacity
Model
Line Size
Connection
Size
(Inch I.D.)
[mm]
Line Size
(Inch O.D.)
[mm]
Outdoor Unit
BELOW
Indoor Coil (Heat Pumps)
Total
Equivalent
Length - Feet [m]
5/8” [15.88]
Same as Liquid Line Size Table
-024
3/4” [19.05]
3/4” [19.05]*
Same as Liquid Line Size Table
NA
7/8” [22.23]
NA
5/8” [15.88]
Same as Liquid Line Size Table
-036
3/4” [19.05]
3/4” [19.05]*
Same as Liquid Line Size Table
7/8” [22.23]
NA
5/8” [15.88]
Same as Liquid Line Size Table
-048
7/8” [22.23]
3/4” [19.05]
Same as Liquid Line Size Table
7/8” [22.23]*
Same as Liquid Line Size Table
3/4” [19.05]
Same as Liquid Line Size Table
-060
7/8” [22.23]
7/8” [22.23]*
Same as Liquid Line Size Table
1-1/8” [28.58]
Same as Liquid Line Size Table
25 [7.62]
50 [15.24]
75 [22.86]
100 [30.48]
125 [38.1]
150 [45.72]
Suction Line Size
NOTES:
Using suction line larger than shown in chart will result in poor oil return and is not recommended.
N/A = Application Not Recommended
*Standard Line Size
Summary of Contents for PRL-series
Page 52: ...FIGURE 11 WIRING DIAGRAM FOR 2 3 4 TON 19 0 WIRING DIAGRAMS 52 ...
Page 53: ...FIGURE 12 WIRING DIAGRAM FOR 5 TON 53 ...
Page 54: ...54 ...
Page 55: ...55 ...
Page 56: ...56 CM 1108 ...