background image

www.fmiproducts.com

113097-01M

21

1.  Shut off unit, including pilot. Allow unit to 

cool for at least thirty minutes.

2.  Inspect burner, pilot and primary air inlet 

holes on orifice holder for dust and dirt 

(see Figure 25).

3.  Blow air through the ports/slots and holes 

in the burner.

4.  Check  the  orifice  holder  located  at  the 

end  of  the  burner  tube  again.  Remove 

any large particles of dust, dirt, lint or pet 

hair with a soft cloth or vacuum cleaner 

nozzle.

5.  Blow air into the primary air holes on the 

orifice holder.

6.  In case any large clumps of dust have now 

been pushed into the burner repeat steps 

3 and 4.

Clean pilot assembly also. A yellow tip on the 

pilot flame indicates dust and dirt in the pilot 

assembly. There is a small pilot air inlet hole 

about 2" from where the pilot flame comes out 

of the pilot assembly (see Figure 26). With the 

unit off, lightly blow air through the air inlet 

hole. You may blow through a drinking straw 

if compressed air is not available.

CLEANING AND MAINTENANCE

Continued

Figure 25 - Orifice Holder On Outlet 

Burner Tube

Burner Tube

Primary Air 

Inlet Holes

Orifice Holder 

Figure 26 - Pilot Inlet Air Hole

Burner Tube

Pilot Assembly

Pilot Air 

Inlet Hole

Ports/Slots

LOGS

•  If  you  remove  logs  for  cleaning,  refer  to 

Installing Logs,

 page 16, to properly replace 

logs.

•  Replace log(s) if broken or chipped (dime-

sized or larger).

MAIN BURNER

Periodically inspect all burner flame holes with 

the heater running. All slotted burner flame 

holes should be open with yellow flame pres-

ent. All round burner flame holes should be 

open with a small blue flame present. Some 

burner flame holes may become blocked by 

debris or rust, with no flame present. If so, 

turn off heater and let cool. Remove blockage. 

Blocked burner flame holes will create soot.

SERVICE HINTS

When Gas Pressure Is Too Low

•  pilot will not stay lit
•  burners will have delayed ignition
•  heater will not produce specified heat
•  for propane/LP units, propane/LP gas sup-

ply may be low

You may feel your gas pressure is too low. If 

so, contact your local propane/LP or natural 

gas supplier.

TECHNICAL SERVICE

You may have further questions about instal-

lation,  operation,  or  troubleshooting.  If  so, 

contact FMI PRODUCTS, LLC at 1-866-328-

4537. When calling please have your model 

and serial numbers of your heater ready.
You  can  also  visit  FMI  PRODUCTS,  LLC’s 

web site at 

www.fmiproducts.com

.

Summary of Contents for CRL2718NA

Page 1: ...s of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch a...

Page 2: ...is an unvented gas fired heat er It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ven...

Page 3: ...en though no odor exists Make certain you read and understand all warnings Keep this manual for reference It is your guide to safe and proper operation of this heater WARNING Any change to this heater...

Page 4: ...s doors closed If you operate heater with doors closed heat buildup inside fireplace will cause glass to burst Make sure there are no obstructions across openings of fireplace 9 This log heater is des...

Page 5: ...e logs and heater base assembly from carton Note Do not pick up heater base assembly by burners This could damage heater Always handle base as sembly by grate 2 Remove all protective packaging applied...

Page 6: ...ll fireplace plus any adjoining rooms with door less passageways or ventilation grills between the rooms 1 Determine the volume of the space length x width x height Length x Width x Height __________c...

Page 7: ...itional fresh air Your options are as follows A Rework worksheet adding the space of an adjoining room If the extra space provides an unconfined space remove door to adjoining room or add ventilation...

Page 8: ...d one within 12 of the floor Connect these items directly to the outdoors or spaces open to the outdoors These spaces include attics and crawl spaces Follow the National Fuel Gas Code ANSI Z223 1 NFPA...

Page 9: ...42 INSTALLATION Continued Figure 4 Minimum Clearance for Combustible to Wall Minimum 16 from Side Wall Example WARNING Never install the heater in a bedroom or bathroom unless installed as a vented a...

Page 10: ...above fireplace opening is not needed Go to Installing Damper Clamp Accessory for Vented Operation page 12 Minimum Noncombustible Material Clearances If Not Using Mantel Note If using a mantel proceed...

Page 11: ...f the following operate logs only with flue damper open raise mantel to an acceptable height remove mantel Floor Clearances A If installing appliance on the floor level you must maintain the minimum d...

Page 12: ...Clamp Damper Damper Clamp Damper INSTALLING DAMPER CLAMP ACCESSORY FOR VENTED OPERATION Note When used as a vented heater ap pliance must be installed only in a solid fuel burning fireplace with a wo...

Page 13: ...heater base 7 Mark screw locations through holes in mounting brackets see Figure 12 If installing in a brick bottom fireplace mark screw locations in mortar joint of bricks 8 Remove heater base from...

Page 14: ...ing may be used in certain areas Check your local codes Use pipe of 1 2 diameter orgreatertoallowpropergasvol ume to heater If pipe is too small undue loss of volume will occur Installation must inclu...

Page 15: ...e control valve and equip ment shutoff valve from gas supply piping system Pressures in excess of 1 2 psig will damage heater regulator 2 Cap off open end of gas pipe where equip ment shutoff valve wa...

Page 16: ...er see To Turn Off Gas to Appliance page 19 Figure 16 Checking Gas Joints Propane LP Gas Models Equipment Shutoff Valve Propane LP Supply Tank Thermostat Gas Valve or Control Valve Location Figure 17...

Page 17: ...rossover logs on top of back log and front log Make sure pins on front and back are inserted into holes on crossover logs see Figure 20 Crossover logs must be placed as shown in Figure 210or holes wil...

Page 18: ...e 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety information column 1 If you don t smell gas go to the next step FOR YOUR SAFET...

Page 19: ...To leave pilot lit and shut off burners only turn control knob clockwise to the HI position then press in and turn clock wise to PILOT position WARNING Do not operate heater between PILOT and HI posi...

Page 20: ...s not touching the thermocouple This will cause the thermo couple to cool When the thermocouple cools the heater will shut down If pilot flame pattern is incorrect as shown in Figure 24 WARNING Turn o...

Page 21: ...et Holes Orifice Holder Figure 26 Pilot Inlet Air Hole Burner Tube Pilot Assembly Pilot Air Inlet Hole Ports Slots LOGS If you remove logs for cleaning refer to Installing Logs page 16 to properly rep...

Page 22: ...leted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cab...

Page 23: ...pressed in 30 seconds 3 Fully open equipment shut off valve 4 A Contact local propane LP or natural gas com pany B Clean ODS pilot see Cleaning and Maintenance page 20 or replace ODS pilot assembly 5...

Page 24: ...O or position 1 and let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local propane LP or natural gas company 3 Observeminimuminstallation clearances se...

Page 25: ...ve 1 Take apart gas tubing and remove foreign matter 2 Locate and correct all leaks see Checking Gas Con nections page 15 OBSERVED PROBLEM Heater produces unwanted odors Gas odor even when control kno...

Page 26: ...Piezo Manifold Pressure 8 W C Inlet Gas Pressure in of water Maximum 14 W C Minimum 11 W C CRL3124PA 16 000 31 500 Btu hr Variable Gas Type Propane LP Ignition Piezo Manifold Pressure 8 W C Inlet Gas...

Page 27: ...RODUCTS LLC at 1 866 328 4537 for information You can also write to the address listed on the back page of this manual DAMPER CLAMP GA6080 Permanently opens chimney flue damper for vented operation Ca...

Page 28: ...www fmiproducts com 113097 01M 28 PARTS Variable Manually Controlled Seasonal Oak Models CRL2718PA CRL2718NA CRL3124PA AND CRL3124NA 4 12 6 10 11 6 7 6 5 1 8 9 15 14 16 19 21 18 13 19 17 20 18 2 3B 3A...

Page 29: ...99056 20 099056 19 099056 18 Burner Orifice 1 11 111124 01 111124 01 111124 01 111124 01 Burner Retainer Spring 1 12 102963 02 102963 02 102773 03 102773 03 Burner 1 13 119583 01 119583 03 119583 01 1...

Page 30: ...______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ____...

Page 31: ...______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ____...

Page 32: ...product and or FMI PRODUCTS LLC who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty Travel handling transportation diagnostic mat...

Reviews: