background image

www.fmiproducts.com

111161-01L

10

CHECK GAS TyPE

Use the correct gas type (natural or propane/

LP) for your unit. If your gas supply is not cor-

rect, do not install heater. Call dealer where 

you bought heater for proper type heater.

 WARNING: This appliance is 

equipped for either natural gas 

or propane/LP gas but not both. 

Gas type is indicated on the rat

-

ing plate. Field conversion is not 

permitted.

INSTALLATION AND CLEARANCES

(Vent-Free Operation Only)

  WARNING:  Maintain  the 

minimum clearances. If you can, 

provide greater clearances from 

floor, ceiling and adjoining wall.

MINIMUM FIREPLACE CLEARANCE

 

TO COMBUSTIBLE MATERIALS

 

Side Wall 16" 

Ceiling: 42"

LOG SIZING REQUIREMENTS

 

 

Minimum Firebox

  Log 

 

 

Front  Rear *

 Size  Height  Depth  Width  Width

  24" 

17" 

13" 

28" 

21"

  30" 

17" 

13" 

34" 

24"

* Measured at 13" depth.
Carefully follow the instructions below. This 

will ensure safe installation into a masonry, 

UL127-listed manufactured fireplace or listed 

vent-free firebox.

Minimum Clearances for Side Combus

-

tible Material, Side Wall and Ceiling 

A.  Clearances from the side of the fireplace 

cabinet to any combustible material and 

wall should follow diagram in Figure 4.

 

Example:

 The face of a mantel, bookshelf, 

etc. is made of combustible material and 

protrudes 3 

1

/

2

" from the wall. This com-

bustible material must be 4" from the side 

of the fireplace opening (see Figure 4).

 

Note: When installing your gas logs into 

a  manufactured  firebox,  follow  firebox 

manufacturer’s instructions for minimum 

clearances to combustible materials.

INSTALLATION

Continued

Figure 4 - Minimum Clearance for 

Combustible to Wall

*Minimum 16" from Side Wall

*

Example

Minimum Noncombustible Material 

Clearances

If Not Using Mantel

Note: If using a mantel, proceed to If Using 

Mantel, page 11. If not using a mantel, follow 

the information below.

You  must  have  noncombustible  material(s) 

above the fireplace opening. Noncombustible 

materials  (such  as  slate,  marble,  tile,  etc.) 

must be at least 1/2" thick. With sheet metal, 

you must have noncombustible material be-

hind it. Noncombustible material must extend 

at least 8" up. If noncombustible material is 

less than 12", you must install the fireplace 

hood accessory. See Figure 5, page 11, for 

minimum clearances.

IMPORTANT:

 If you cannot meet these mini-

mum  clearances,  you  must  operate  heater 

with chimney flue damper open. Go to 

Install-

ing  Damper  Clamp Accessory  for  Vented 

Operation, 

page 12.

B.  Clearances from top of fireplace opening 

to ceiling should not be less than 42".

NOTICE: Manual control heaters 

may be used as a vented product. 

If so, you must always run heater 

with chimney flue damper open. 

If  running  heater  with  damper 

open, noncombustible material 

above fireplace opening is not 

needed. Go to 

Installing Damper 

Clamp  Accessory  for  Vented 

Operation

, page 12.

Summary of Contents for CCL3924NRA

Page 1: ...ycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a quali fi...

Page 2: ...fired heat er It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ven tilation section on...

Page 3: ...ough no odor exists Make certain you read and understand all warnings Keep this manual for reference It is your guide to safe and proper operation of this heater WARNING Any change to this heater or i...

Page 4: ...er is designed to be smoke less If logs ever appear to smoke turn off heater and call a qualified service person Note During initial operation slight smok ing may occur due to log curing and heater bu...

Page 5: ...licensed plumber or gas fitter in the Commonwealth of Massachusetts Sellers of unvented propane or natural gas fired supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upo...

Page 6: ...anever Newmaterials increasedinsulationand new construction methods help reduce heat loss in homes Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm ai...

Page 7: ...g room is supplied with grills or openings add the volume of these rooms to the total volume of the space 2 Multiply the space volume by 20 to determine the maximum Btu Hr the space can support ______...

Page 8: ...and Ventilation for required size of ventilation grills or ducts Ventilation Air From Outdoors Provide extra fresh air by using ventilation grills or ducts You must provide two perma nent openings on...

Page 9: ...s without enough ventilation air may cause mildew to form from too much moisture See Air for Combustion and Ventila tion page 6 Installation NOTICE Thisheater isintended for use as supplemental heat U...

Page 10: ...ble material must be 4 from the side of the fireplace opening see Figure 4 Note When installing your gas logs into a manufactured firebox follow firebox manufacturer s instructions for minimum clearan...

Page 11: ...A6053 see Accessories page 31 Less than 8 Noncombustible material must be extended to at least 8 See Between 8 and 12 above If you can not extend material you must operate heater with flue damper open...

Page 12: ...lace Clearances Above Combustible Flooring Figure 8 Minimum Fireplace Clearances If Installed at Floor Level INSTALLING DAMPER CLAMP AC CESSORY FOR VENTED OPERATION Note When used as a vented heater a...

Page 13: ...e provided with heater approved flexible gas hose not provided if allowed by local codes sealant resistant to propane LP gas not provided electric drill with 3 16 masonry drill bit Note Install option...

Page 14: ...y to male NPT threads This will prevent excess sealant from going into pipe Excess sealant in pipe could result in clogged heater valves Installation Continued Figure 13 External Regulator With Vent P...

Page 15: ...or fittings CHECKING GAS CONNECTIONS WARNING Testallgaspiping and connections internal and external to unit for leaks after installing or servicing Correct all leaks at once WARNING Never use an open...

Page 16: ...Closed Equipment Shutoff Valve Figure 16 Checking Gas Joints Propane LP Tank Equipment Shutoff Valve Control Valve Location Figure 17 Checking Gas Joints Gas Meter Equipment Shutoff Valve Control Valv...

Page 17: ...ng It is very important to install these logs exactly as instructed Do not modify logs Only use logs supplied with heater 1 Place front log 1 on grate fingers Make sure front log rests firmly between...

Page 18: ...ON Figure 21 Installing Crossover Log 4 CCL3930PR NRA Shown Log 2 Log 3 Pegs Figure 22 Installing Crossover Log 5 CCL3930PR NRA Shown AUTO OFF ON 7 Figure 24 Installing Crossover Log 7 to Models CCL39...

Page 19: ...WARNING Burners will come on automatically within one minute when the selector switchisintheONpositionafter the pilot is lit FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not fol low these in...

Page 20: ...light pilot The pilot is attached to the front burner If needed keep pressing ignitor button until pilot lights Note If pilot does not stay lit contact a qualified service person or gas supplier for...

Page 21: ...here be tween HI and LO Slide the selector switch to the REMOTE position see Figure 27 Note The burner may light if hand held re mote was on when selector switch was last turned off You can now turn t...

Page 22: ...Yourlocal computer store hardware store or home center may carry compressed air in a can If using com pressed air in a can please follow the directions on the can If you don t follow directions on th...

Page 23: ...hen in stalled 5 Depleted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tub...

Page 24: ...After ODS pilot lights keep control knob pressed in 30 seconds 3 Fully open equipment shut off valve 4 A Contact local natural or propane LP gas company B Clean ODS pilot see Cleaning and Maintenance...

Page 25: ...on and Ventilation require ments page 6 1 Turn control knob to LO position and let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local natural or propan...

Page 26: ...ocate and correct all leaks see Checking Gas Con nections page 15 2 Replace control valve 1 Take apart gas tubing and remove foreign matter 2 Locate and correct all leaks see Checking Gas Con nections...

Page 27: ...0NRA Rating Variable 20 000 39 000 Btu Hr Type Gas Natural Ignition Piezo Manifold Pressure 3 5 W C Inlet Gas Pressure in of water Max 10 5 W C Min 5 W C CCL3924PRA and CCL3930PRA Rating Variable 20 0...

Page 28: ...27 18 23 12 11 14 4 5 1 2 17 10 21 20 22 6 7 3 9 20 16 8 15 29 28 28 25 26 O F F P I L O T O N H I L O O F F P I L O T O N H I L O 24 31 13 Parts MODELS CCL3924PRA CCL3924NRA CCL3930PRA and CCL3930NRA...

Page 29: ...Pilot Tube 1 16 103781 02 103781 02 Gas Control Valve LP 1 103781 01 103781 01 Gas Control Valve NG 1 17 103345 01 103345 01 103345 01 103345 01 Lower Bracket 1 18 M11084 38 M11084 38 M11084 38 M1108...

Page 30: ...elayed ignition heater will not produce specified heat propane LP gas supply may be low You may feel your gas pressure is too low If so contact your local propane LP gas supplier If this product is mi...

Page 31: ...FMI PRODUCTS LLC at 1 866 328 4538 for information You can also write to the address listed on the back page of this manual RECEIVER AND HAND HELD THERMOSTAT REMOTE CONTROL KIT MLCR M For all Remote...

Page 32: ...product and or FMI PRODUCTS LLC who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty Travel handling transportation diagnostic mat...

Reviews: