INSTALLATION
Continued
14"
Min.
Combustible
Material
Noncombustible Material
Figure 8 - Minimum Fireplace Clearances
If Installed at Floor Level
Figure 9 - Minimum Fireplace Clearances
Above Combustible Flooring
Noncombustible Material
Hearth
5"
Min.
Combustible
Material
FLOOR CLEARANCES
A. If installing appliance on the fl oor level,
you must maintain the minimum distance
of 14" to combustibles
(see Figure 8).
B. If combustible materials are less than 14"
to the fi replace, you must install appliance
at least 5" above the combustible fl ooring
(see Figure 9).