13
08: EPO logic setting
Interface
Setting
Set up the EPO function control logic.
AO: Active Open (Default). When AO is selected as EPO
logic, it will activate EPO function with Pin 1 and Pin 2 in
open status.
AC: Active Close. When AC is selected as EPO logic, it will
activate EPO function with Pin 1 and Pin 2 in close status.
DIS: Disable the EPO function
00: Exit setting
Interface
Setting
Exit the setting mode.
Steps for setting programmable outlet
Step 1:
Before entering setting mode, the UPS should be in Stand-by
mode (off-charging) and make sure the battery is
connected. The LCD display is shown as right.
Step 2:
Press and hold the “Selection” button for 3 seconds to enter
Setting mode.