12
02: Programmable outlets enable/disable
Interface
Setting
ENA: Programmable outlets enable (Default)
DIS: Programmable outlets disable
03: Programmable outlets setting
Interface
Setting
Setting the backup time limits in minutes from 0-999 for
programmable outlets which connect to non-critical devices
on battery mode.
04: Maximum charger current setting
Interface
Setting
Set up the maximum charger current.
1/2/4/6/8: setting the maximum charger current at
1/2/4/6/8 Ampere. (Default: 8A)
Note: This setting is only effective for super charger.
06: Autonomy limitation setting
Interface
Setting
Set up backup time on battery mode for general outlets.
0-999: setting the backup time in minutes from 0-999 for
general outlets on battery mode.
DIS: Disable the autonomy limitation and the backup time
will depend on battery capacity. (Default)
Note: When setting as “0”, the backup time will be only 10
seconds.
07: Battery total AH setting
Interface
Setting
Set up the battery total AH of the UPS.
7-999: setting the battery total capacity from 7-999 in AH.
Please set the correct battery total capacity if external
battery bank is connected.