IE-SNC-T2114-03 

 

Unscrew four screws of the device lid a remove the lid. If device is already installed to 
measuring system, disconnect leads from terminals. 

 

Connect  SP003  communication  cable  to  the  device.  Display  must  light  up,  or  at  least 
must  light  up  all  symbols  for  one  second  (if  LCD  was  switched  OFF  by  program 
before).  

 

Run  installed  TSensor  program  and  select  corresponding  communication  COM  port 
(as described above). 

 

When new setting is saved and finished, disconnect the cable from the device, connect 
leads into its terminals and place the lid back to the device. 

 

Error States of the device 

Device  continuously  checks  its  state  during  operation.  In  case  error  is  found  LCD  displays 
corresponding error code: 

Error 0 

There is a reading „Err0“ on LCD display. 
Check  sum  error  of  stored  setting  inside  device’s  memory.  Output  value  is  <3.8 mA.  This  error 
appears if incorrect writing procedure to device’s memory occurred or if damage of calibration data 
appeared.  At  this  state  device  does  not  measure  and  calculate  values.  It  is  a  serious  error,  contact 
distributor of the device to fix. 

Error 2 

There is a reading „Err2“ on LCD display. 
Atmospheric  pressure  measurement  error  occurred.  Output  value  is  about  3.8 mA.  Measured 
pressure  value 

with  added  correction  for  altitude

  is  outside  of  range  from  300 hPa  to  1350 hPa 

(from 4.351 PSI to 19.580 PSI) or the pressure sensor is damaged. Please check setting of pressure 
correction for altitude with User’s software. 

Error 4 

There is a reading „Err4“ on LCD display. 
It  is  internal  device  error  during  pressure  sensor  initialization.  Under  this  condition  device  does 
NOT  measure  atmospheric  pressure  Output  value  is  about  3.8 mA.  Pressure  sensor  is  probably 
damaged. It is a serious error, contact distributor of the device. 
 

 

End of operation 

Device itself (after its life) is necessary to liquidate ecologically! 

 

Technical support and service 

Technical support and service is provided by distributor. For contact see warranty certificate 

Summary of Contents for T2114

Page 1: ...turer reserves the right to make technical changes to the device without previous notice Misprints reserved Manufacturer is not responsible for damages caused by using the device in conflict with this manual To damages caused by using the device in conflict with this manual cannot be provide free repairs during the warranty period Read carefully instruction manual before the first device connectio...

Page 2: ...f special setting was not required in the order device is set from the manufacturer to the following parameters value at output I1 4 20 mA corresponds to atmospheric pressure from 800 to 1100 hPa1 correction for altitude 0 hPa absolute pressure display switched ON pressure unit hPa Modification of the setting is possible to do by means of the PC using procedure described at the end of this documen...

Page 3: ...side Electrical system wiring may do only worker with required qualification by rules in operation Setting of pressure correction for altitude If there is necessary to read value of atmospheric pressure corrected with respect to altitude it is possible to set corresponding pressure offset for this altitude It is possible to do it with Users software This value is then automatically added to measur...

Page 4: ...ted to the lowest pressure output value displayed at upper LCD line Here 4 mA corresponds to 800 hPa Press button again to get value for upper point similarly as at previous point Here 20 mA corresponds to 1100 hPa Notice during info mode no measurement and no output current generation proceed The device stays at info mode 15 s and then automatically goes back to measuring cycle Readings on LCD di...

Page 5: ...ering from the top side Electromagnetic compatibility complies EN 61326 1 Not allowed manipulations It is not allowed to operate the device under other than specified conditions in technical parameters Devices are not designed for locations with chemically aggressive environment Do not use the device in an explosive environment Storing conditions temperature 30 to 80 C humidity 0 to 100 RH without...

Page 6: ...ocedure to device s memory occurred or if damage of calibration data appeared At this state device does not measure and calculate values It is a serious error contact distributor of the device to fix Error 2 There is a reading Err2 on LCD display Atmospheric pressure measurement error occurred Output value is about 3 8 mA Measured pressure value with added correction for altitude is outside of ran...

Page 7: ...IE SNC T2114 03 7 Appendix A ...

Reviews: