background image

 

  IE-LOG-S5141-01 

Switched  ON  logger  permanently  (with  10  s  interval)  updates  memory  of 
minimum and maximum values of each measured quantity. If displaying of 
MIN/MAX values is selected, minimum measured values are displayed step 
by step (indicated by symbol MIN) and then similarly maximum measured 
values  of  all  quantities  (indicated  by  symbol  MAX).  The  entire  cycle  is 
repeated periodically, i.e. reading of actual measured values follows. 

 

If display is switched OFF,

 all above readings are displayed up to estimated 

remaining battery  capacity  and then display  goes out.  If logger is  switched 
ON symbol LOG is displayed (it blinks if memory occupation is higher than 
90%). 

 

If display is OFF and logger is in mode when record runs only when alarm is 
active,  the  LOG  symbol  is  replaced  by  adjacent  symbol  "–"  (hyphen).  It 
appears in case, all measured values are inside of adjusted alarm limits and 
data logging therefore does not run. Displayed symbol indicates logger is ON. 

 
If  information  on  actual  measured  values  is  needed,  it  is  possible  anytime  to  display  reading 

display by means of the magnet (only if communication adapter is not connected permanently). Plug 
magnet  into  guide  slots  from  logger  front  side  for  approximately  4  s  and  wait  till  reading  on  the 
display  appears.  If  logger  has  enabled  the  function  switch  OFF  by  magnet  or  the  function  reset 
memory of  MIN/MAX  values by magnet, do not  remove magnet  from guide slots before decimal 
point symbol goes out – logger would be switched OFF (memory of the MIN/MAX values would be 
erased)!  Display  reading  initialized  by  magnet  goes  out  automatically  after  30  s.  Remove  magnet 
from slots anytime during actual reading is ON or later. 

 
Temporary displaying of actual reading by magnet 

 

 
 
 
 
 
 

 

 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for S5141

Page 1: ...LOGGER S5141 Three channel 0 5 Vdc datalogger with internal temperature sensor and display Instruction Manual...

Page 2: ...nction Also memory alarm mode is selectable when alarm is indicated permanently till alarm memory reset Alarm function is enabled or disabled for each channel individually Logging mode can be adjusted...

Page 3: ...normal environment accordingly to appendix NM AE1 AN1 AR1 BE1 Operational position negligible Logger installation by self adhesive Dual Lock applied to clean flat surface Not allowed manipulation inco...

Page 4: ...er automatic switching ON or disable this option select if record runs permanently or only if alarm is active if alarms are about to be applied set both limits for each measured quantity and enable al...

Page 5: ...the display in usual operation logger switched ON After switching ON the logger all LCD symbols are displayed for checking the display Then actual date and time in logger is displayed for approximate...

Page 6: ...bol is replaced by adjacent symbol hyphen It appears in case all measured values are inside of adjusted alarm limits and data logging therefore does not run Displayed symbol indicates logger is ON If...

Page 7: ...lled in non cyclic logging mode logger is switched OFF and message MEMO FULL appears on the LCD It appears also if logger is operated with switched OFF display New initialization of logger can occur i...

Page 8: ...ogger OFF by magnet The procedure is identical with the above procedure for switching ON If decimal point does not appear after 1 s it is necessary remove the magnet and repeat the procedure Reset of...

Page 9: ...cially the real time clock in logger Attention inserted battery with incorrect polarity causes logger damage put the lid back again and screw four screws Be careful to have the rubber sealing properly...

Reviews: