             MOUNTING 

 

Install in a site which does not experience direct sunlight; 

 

Make sure you carry out the connection procedure WITHOUT the mains voltage (230 V) and batteries connected; 

 

Observe the polarity of the batteries; 

 

Connect the 230 V power supply and earth connection; 

 

Check all the connections before powering up the device. 

Description of the power supply unit elements 

No. 

Description 

Label 

Power supply  230 V  50 Hz  

L - N - Earth 

Battery terminals 

Battery 

Temperature sensor 

 

Connector 1 

Out 1 

Connector 2 

Out 2 

General fault output 

Gen FLT 

Power supply fault output 

Mains FLT 

External fault input 

Ext FLT 

Green LED 

Mains 

10 

Yellow LED 

Batteries 

11 

Diode indication 

Z201 

12 

Tamper connector 

Z204 jumper 

13 

External indication input 

J201 

 
The fault output relays (Gen FLT and Mains FLT) have NC and NO contacts. 
The external fault input must be closed to obtain the steadily lit yellow LED fault indication and the switching of the General 
Fault output relay. 

If you want to use the door opening tamper, connect an NC contact on connector Z204; otherwise 
leave the jumper closed (default). 
 

 

B201 

mains circuit (delayed T) FUSE 

B101, B102 

output circuits (fast-blow F) FUSES 

B103 

battery circuit (fast-blow F) FUSE 

 

ACTIVATION 

 

If all the connections have been performed correctly, the status indications should be those listed in the table below, column 1. 
Before using the power supply unit, please carry out a further two tests.  
 
1.  Backup power supply test (backup battery): 

Cut off the main power supply; the power supply unit should switch to battery operation mode. Check the output 
voltage on the battery fastons. 
If the B201 mains fuse is removed, the condition can only be detected after 10 minutes.  
The GEN FLT relay intervenes with a delay of 5 seconds. 

2.  Battery presence test: 

When the power is supplied from the 230 V mains, break the battery circuit by disconnecting one of the 2 poles 
connected to it. This condition will be detected the next time a test is carried out, which may take up to 10 minutes. 

Summary of Contents for ZSP100 Series

Page 1: ...NTATION SUPPL MENTAIRE EXTRA VOEDINGSEENHEID ZSP100 Alimentatore per Sistemi rivelazione incendio Conforme Norma EN 54 4 1997 A1 2002 A2 2006 2 Certificato di conformit CNBOP No 1438 CPD 0163 Certific...

Page 2: ...CARICA BATTERIE DIMENSIONI ZSP100 2 5A 18 2 5 A 1 0 A 7 20Ah 395x356x96mm ZSP100 5 5A 18 5 5 A 1 0 A 7 20Ah 395x356x96mm Fig 1 Vista frontale e laterale dell alimentatore Gli alimentatori nella parte...

Page 3: ...scita Guasto Generale Se si vuole utilizzare il tamper apertura portella collegare un contatto NC sul connettore Z204 in caso contrario lasciare il jumper chiuso default B201 FUSIBILE circuito di rete...

Page 4: ...di batteria collegata inferiore a 10 V Resistenza del fusibile del circuito della batteria troppo alta 250m Fusibile uscita bruciato Tensione della batteria al di sotto di 22V con l alimentazione di...

Page 5: ...r wall mounting TECHNICAL CHARACTERISTICS POWER SUPPLY UNIT MAX CURRENT OUTPUT LOAD CURRENT BATTERIES DIMENSIONS ZSP100 2 5 A 18 2 5 A 1 0 A 7 20 Ah 395x356x96 mm ZSP100 5 5 A 18 5 5 A 1 0 A 7 20 Ah 3...

Page 6: ...fault indication and the switching of the General Fault output relay If you want to use the door opening tamper connect an NC contact on connector Z204 otherwise leave the jumper closed default B201...

Page 7: ...supply No battery or the voltage of the battery connected is under 10 V Battery circuit fuse resistance too high 250 m Output fuse blown Battery voltage under 22 V with mains power supply present 1 0...

Page 8: ...ll es en saillie CARACT RISTIQUES TECHNIQUES ALIMENTATION COURANT MAXI DE SORTIE COURANT DE CHARGE BATTERIES DIMENSIONS ZSP100 2 5A 18 2 5 A 1 0 A 7 20 Ah 395x356x96mm ZSP100 5 5A 18 5 5 A 1 0 A 7 20...

Page 9: ...jaune allum e et l change du relais de sortie Panne G n rale Pour utiliser l autoprotection d ouverture du volet brancher un contact NF sur le connecteur Z204 Dans le cas contraire laisser le cavalier...

Page 10: ...ou la tension de la batterie connect e est inf rieure 10 V R sistance du fusible du circuit de la batterie trop lev e 250 m Fusible de sortie grill Tension de la batterie inf rieure 22 V en pr sence d...

Page 11: ...alimentadores se han dise ado para montarse en la pared CARACTER STICAS T CNICAS ALIMENTADOR SALIDA EN CORRIENTE M X CORRIENTE DE CARGA BATER AS DIMENSIONES ZSP100 2 5 A 18 2 5 A 1 0 A 7 20 Ah 395x35...

Page 12: ...marillo y el intercambio del rel de salida de aver a general Si se desea utilizar el tamper de apertura de la tapa conectar un contacto normalmente cerrado al conector Z204 en caso contrario dejar el...

Page 13: ...imentaci n defectuosa Ninguna bater a o la tensi n de la bater a conectada es inferior a 10 V Resistencia del fusible del circuito de la bater a demasiado alta 250 m Fusible de la salida fundido Tensi...

Page 14: ...e TECHNISCHE EIGENSCHAPPEN VOEDINGSEENHEID MAX UITGANGSSPANNING LAADSTROOM BATTERIJEN AFMETINGEN ZSP100 2 5A 18 2 5 A 1 0 A 7 20Ah 395x356x96mm ZSP100 5 5A 18 5 5 A 1 0 A 7 20Ah 395x356x96mm Fig 1 Fro...

Page 15: ...ais Algemene storingsuitgang Als u de tamper opening frontpaneel wilt gebruiken sluit dan een NC contact aan op de connector Z204 Zo niet laat de jumper dan gesloten default Indicatie zekeringen B201...

Page 16: ...spanning van de aangesloten batterij is lager dan 10 V De zekeringsweerstand van het circuit van de batterij is te hoog 250m Uitgangszekering verbrand Batterijspanning lager dan 22V terwijl de netvoe...

Page 17: ...Comelit Group Spa Via Don Arrigoni 5 24020 Rovetta S Lorenzo Italy Tel 39 0 346 750011 Fax 39 0 346 71436 www comelitgroup com...

Reviews: