41CPE112 Addressable Fire Alarm Panel – Installation and Programming Manual
26
7.2. Zones Menu
This menu allows the installer to review and change the status of every zone. In the ‘ZONES’ menus the installer can
test and enable/ disable the zones. Up to 48
zone numbers are available for settings. The currently edited zone
number is blinking. The menu is accessible from levels 2 and 3.
After entering the menu the screen displays:
The screen displays the current status of every zone with its name (if entered). The editable zone number is blinking.
Description of the zone status:
•
NORMAL –
The zone is in normal operation state.
•
DISABLED –
The zone is disabled. See item 7.2.3.
•
TEST –
The zone is in test mode. See item 7.2.2.
•
FIRE –
A device in the zone is in fire.
•
PRE ALARM –
The zone is in preliminary alarm mode. See
the description for ‘2DEVICES’ and ‘DOUBLE’ action modes - item
7.2.6.
•
FAULT –
Trouble in the zone – lost device, broken circuit, etc.
7.2.1 General Submenus
From the main screen of ZONES menu use the functional digit buttons for direct entry to: (1) GO TO and (2) DEV.
VIEW submenus.
•
Submenu (1) GO TO.
Enter the zone number you want to go. After pressing the button the screen displays:
Use up and down arrows to select zone number. Confirm with
‘ENTER’ button. The system will automatically go back to the main
screen of ZONES menu as the number of the zone is blinking.
•
Submenu (2) DEV. VIEW.
The submenu shows information about the total number of the devices in the
respective zone. From the main screen of ZONES menu, select a zone number and press button (2). A
detailed list with address and name of the respective devices is displayed also. The screen displays
information about the total number of the devices in the selected zone regardless of their current state.
Example:
Use the arrow buttons to review the list of all devices associated to
the zone.
Exit to the main screen of ZONES menu is pressing button ENTER or
CANCEL.
7.2.2 Zones Testing
From the main screen of ZONES menu, select a zone number using the up and down arrow buttons and press button
(3) TEST.
The system will ask for confirmation whether to run the test only for
the selected zone number (button (2) THIS) or for all zones in the
system (button (3) ALL).
The zone(s) status is changed to TEST mode. The LED ‘Test’ is
lighting on permanently.
During the test mode the installer activates detectors in the zone (applies heat or smoke) to check their proper
operation. The panel confirms the receiving of fire alarm messages with short sound signals and the number of the
tested zone is blinking. Note: During testing zones 17-48 will blink the LED ‘Test’ only!
To stop the zone test, press the (3) ‘STOP TEST’ functional button. The zone returns to normal operation mode.
After completing the zone testing, reset the panel, as described in item 6.9.