6

Example
To program key locking after 3 errors without sending an alarm, enter in sequence:

• 

0 E 

start procedure

• 

12345 E  supercode

• 

5 E 

error function

• 

number of allowed errors

• 

0 E 

do not send alarm

Programming the allowed errors number

This allows you to set the number of code entry errors allowed before the locking function is activated. If, for example, you 

set a value of 3, on the third incorrect code entry the key is locked for a period of 1 minute. You can also send an alarm signal 

(output 

AL

+), after the allowed number of errors, if this is provided for during programming. To send the alarm, program “

1

” 

during the procedure, otherwise program “

0

” (see below). 

An incorrect code entry is the entry of a code not stored during programming, followed by “

E

”.

Programming the allowed errors number:

 1. 

Enter “

0

” and “

E

” (start programming procedure code).

 2. 

Check that the LED has lit up.

 3. 

Enter the 

supercode

 (see 

"Entering the supercode"

), then “

E

”.

 4. 

Enter the number “

5

” (error lock function) followed by “

E

”.

 5. 

Enter the allowed number of errors (1-9), but 

DO NOT

 enter “

E

”.

 6. 

Enter: “

1

” “

E

” to send an alarm when the key is locked; “

0

” “

E

” if you do not wish to send an alarm.

 7. 

The LED should now turn off.

Example
To set the activation time to 10 seconds, enter in sequence:

• 

0 E 

start procedure

• 

12345 E  supercode

• 

6 E 

Remote Key timing function

• 

10 E 

relay activation time

Programming the relay 1 activation delay for a remote key input

This procedure sets the activation time for relay 1 on a remote input. Values from 1 to 99 can be set.  

The default timing is 5 seconds.

Actuator function

One of the relays of 3348B can be used on the generic actuator command originating from the Simplebus Bus.  

Special programming is required on the external unit as described in the TMs for Art. 4680, 4680C, 4681 and for 1621, 1622.
Programming the actuator function:

 1. 

Enter “

0

” and “

E

” (start programming procedure code).

 2. 

Check that the LED has lit up.

 3. 

Enter the 

supercode

 (see 

"Entering the supercode"

), then “

E

”.

 4. 

Enter the number “

7

” ("actuator" function) followed by “

E

”.

 5. 

Enter the number of the relay to be associated with the command (1-2) followed by “

E

”. 

 6. 

Enter a number from 

1

 to 

99

 to indicate the monostable mode seconds value, or enter "

0

" if you want bistable mode, 

followed by “

E

”.

 7. 

The LED should now turn off.

Summary of Contents for 3348B

Page 1: ...EN PROGRAMMING MANUAL Digital electronic key module Art 3348B 3348BM Passion Technology Design...

Page 2: ...first programming 4 Using relay codes 4 Cancelling relay codes 4 Bistable Monostable operation 5 Anti coercion function 5 Programming the allowed errors number 6 Programming the relay 1 activation del...

Page 3: ...supercode is the first operation because all subsequent steps depend on it We recommend using a short easy to remember supercode or noting it down on a sheet of paper Procedura di inserimento del supe...

Page 4: ...entering 55127 E In this example the operating mode has been set to 0 in other words bistable on off To activate monostable operation see Bistable Monostable operation Up to 400 codes can be set rela...

Page 5: ...off Example To set an anti coercion code of 3 enter in sequence 0 E start procedure 12345 E supercode 4 E anti coercion function 3 E anti coercion code Example If relay 1 was activated with code 55127...

Page 6: ...9 but DO NOT enter E 6 Enter 1 E to send an alarm when the key is locked 0 E if you do not wish to send an alarm 7 The LED should now turn off Example To set the activation time to 10 seconds enter i...

Page 7: ...uiting terminals CK and for example via a timer makes it possible to activate relay 1 without entering the relay code but by simply pressing the key button REMOTE KEY INPUT RK Closing this contact wit...

Page 8: ...Yes Contact capacity 24V AC DC MAX Service output max 100 mA Switch Switch C on the back of the module for selecting the LED lighting colour Leave the switch set to OFF for Simplebus systems Operatin...

Page 9: ...9...

Page 10: ...w w w c o m e l i t g r o u p c o m Via Don Arrigoni 5 24020 Rovetta BG Italy 1 ST edition 07 2017 code 2G40001935 C E R T I F I E D M A N A G E M E N T S Y S T E M S...

Reviews: