Comdel CLF5000/PLL Manual Download Page 15

 

14 

Hall effect devices (HE1-HE4) to separately monitor the DC currents feeding each 1250 watt RF power 
amplifier. 

 

C.  Front Panel Control Board   

 

The front panel control board (Figure FA0600RX) has six parts, a frequency controlled, pulse-width 
modulator, circuitry for output power control, monitoring circuitry for protection, frequency measuring 
circuitry, metering circuitry, and remote interface circuitry.   
 
The frequency controlled pulse-width modulator U1 provides the digital drive signals that run the four  
1250 Watt power amplifiers.  This circuit determines the RF output frequency and RF output power.  This 
IC also provides a soft-start function that slowly (1 second) ramps the power up to the setpoint when RF is 
enabled.  R35, R36, and C11 and the voltage applied to varactor diodes D54 & D64 determine the output 
frequency.  Voltage to the non-inverting input Pin 2 of U1 determines the PA drive pulse-width  
(output power). 
 
The power control circuitry smoothes output power and stabilizes it against line and load variations.  
Control is achieved through U3D, the OP400 operational amplifier.  This op-amp compares the delivered 
power signal (from the power monitor board, FA0132RX) to that of the DC reference level (setpoint) at the 
summation point of R24 & R32.  The setpoint is from either the front panel potentiometer or from Pin 22(+) 
& 9(-) of the rear panel ‘D’ connector as determined by LOCAL/REMOTE relay K2. 
 
Monitoring circuitry for power amplifier protection is composed of five parts:  RF output transistor over-
voltage control, over-current control, reflected power control, peak power control, and over-temperature 
control.  These separate functions are controlled respectively by U5D, U5A&B, U5D, U5C, and K3.  In 
each circuit, RF output is limited by reducing setpoint at summing junction R24 & R32  The over-
temperature circuit also disables RF output and stays latched until the RF enable signal from either front 
panel toggle or rear panel Pins 17 and 4 is turned off. 
 
The output frequency of the pulse-width modulator U1 is monitored by a frequency to voltage converter, 
U8.  The circuit is calibrated by pot R95. 
 
Four-way meter switch S2C enables the user to monitor delivered power, reflected power, output 
frequency, and setpoint.  Op -amp U4B serves as a high input impedance buffer amplifier for the front panel 
meter.  Meter calibration is provided by R45. 
 
Remote control analog interfaces are provided by op-amps U3B, U2C, U2A, & U2B.  These op-amps 
provide differential inputs (setpoint in) and outputs (delivered power, forward, & reflected power) 
respectively.  Opto-isolators ISO1D, ISO1C, ISO1B provide digital inputs (RF ENABLE, 
REMOTE/LOCAL SELECT, DELIVERED/FORWARD POWER CONTROL) and ISO2B, ISO2A, & 
ISO1A provide digital outputs (OVERTEMP, MAX POWER, RF OUTPUT ENABLED) respectively. 

 

D.  LF1250 Power Amplifier 

 

There are four LF1250 power amplifiers (FA0003RX) in the CLF5000/PLL.  This amplifier is an eight 
device push-pull Class ‘D’ amplifier, with all devices mounted on a water-cooled copper heatsink.  Each 
device (transistor) is rated to produce over 300 Watts of power, giving a total potential output power of 
2500 watts per amplifier.  Four of these amplifiers are used in the CLF5000/PLL to give a large margin of 
reliability and immunity to large load impedance fluctuations and gives the CLF5000/PLL the ability to 
deliver large amounts of power into less than ideal load conditions.  The output devices are FETs with 
paralleled gates.  The gate drive consists of two FET gate drive ICs U1 & U2.  Peak voltage detector diodes 
D9 & D10 are used by the front panel monitoring circuitry to limit peak voltages seen by the devices.  The 
output impedance of the LF1250 amplifier is about 15 ohms. 

 

Summary of Contents for CLF5000/PLL

Page 1: ...ed FA0600RF to RG per RA RB ECO CLF5000 PLL RF GENERATOR Copyright 2001 by Comdel Inc The information contained in this manual is proprietary to Comdel Inc and is protected by copyright and trademark laws You may not modify copy reproduce republish post transmit or distribute in any way any material from this manual except as may be expressly permitted in writing by Comdel Inc Comdel Inc 11 Kondel...

Page 2: ...ion Requirements VI Operating Instructions 12 A Local Operation B Remote Operation VII Theory of Operation 13 A Interlock System B DC Power Supplies C Front Panel Control Board D LF1250 Power Amplifier E Output Filter F Power Monitor Board VIII Certification 15 IX Figures FP1541RX CLF5000 PLL Electrical Block Diagram FA0302RX Logic DC Regulator assy Schematic FA0509 Hall Effect Current Monitor ass...

Page 3: ...ce of high voltages in or around the unit This symbol indicates that the component or circuit is short circuit protected This symbol indicates the presence of RF energy in or around the unit This symbol indicates a protective earth ground connecting point This label indicates a presence of high voltage in or around the equipment which may cause sever injury or death All appropriate precautions sho...

Page 4: ...NING Hazardous Voltages and RF voltages are present inside this unit which may cause injury or death To prevent electrical shock and or RF burns never operate this equipment with the covers removed Never operate without an appropriate cable connected between the RF output connector on the rear panel and the load CAUTION There are no user or operator serviceable parts inside this equipment Refer al...

Page 5: ...ropriate separation between all interface mains and output circuits in accordance with 5 2 18 of prEN50178 AC Interlock System The low voltage 24 VAC safety interlock circuit is designed to disable the unit in the event of an interlock fault condition At a minimum interlock protection is located at the removable top cover bottom cover and RF output connector safety cover End user s system should p...

Page 6: ...gin 6000 Watts min open loop 2 4 Mismatch Power 1000 watts Minimum Forward Power into any load 2 5 Spurious Output all spurious output to be more than 30 dB below fundamental 2 6 Noise Hum and Ripple Less than 1 at any power level 2 7 Harmonic Output Less than 20 dB below fundamental 2 8 AC to RF Efficiency Better than 70 3 Control 3 1 Control Range 0 10 V range for 0 5000W RF output 3 2 Power lev...

Page 7: ...t power amplifier is built upon a solid copper heatsink block that is naturally corrosion resistant Four 4 fans reduce any possibility of condensation developing internally in the unit 4 4 Two different manufacturer s FET devices to be qualified in specified unit 5 Input Power Requirements 5 1 Electrical input requirements 208 VAC 3 phase 50 60 Hz 20 A 5 2 Manufacturers input specification 5 2 1 N...

Page 8: ...ated digital output representing an output delivered power condition over 5 1KW Pins 20 collector 7 emitter OVERTEMP Opto isolated digital output representing a latched over temp condition RF must be disabled via RF ENABLE IN to reset overtemp latch Pins 19 collector 6 emitter RF ENABLED OUT Opto isolated digital output representing RF has been enabled via RF ENABLE IN Pins 18 cathode 5 anode RF E...

Page 9: ... load 2KW 114 BTU MIN 6840 BTU HR 1 3 Coolant type Water 1 4 Coolant Fittings Swagelok 3 8 tube fitting Tighten per Swagelok specifications using Swagelok Inspection gauge part MS IG 600 1 5 Inlet Air Requirements 5 35 C max 40 95 F Heat Load 500W 29 BTU MIN 1750 BTU HR 2 Storage and Transportation 1 1 Storage Temperature Humidity air pressure 25 to 70 C class 1k4 per prEN50178 5 95 humidity non c...

Page 10: ...omdel immediately CAUTION Breaking the seal or removing the warranty decal from this unit will void the warranty If internal damage is suspected contact factory for assistance IV Maintenance The CLF5000 PLL is designed to run unattended for long periods of time Should service be required the system is designed for quick repair The whole RF section could be replaced in under sixty minutes After a t...

Page 11: ...nnector attached to the 25 pin D Remote I O connector at the rear of the unit and jump AC interlock pins 1 14 2 5 Connect AC power and cooling water 3 Procedure 3 1 Flip CALIBRATE toggle switch on right side of front panel up to CALIBRATE or 450KHz position 3 2 Turn AC power on and enable RF with the front panel RF enable toggle switch 3 3 Turn power setpoint knob to 4000 Watts as indicated by the...

Page 12: ...ad The RF interlock cover must be securely in place to allow operation of the unit 2 Check all cooling system piping and fittings for possible leaks The preferred method is to pressurize the entire cooling system with air and observe any loss of pressure prior to exposing the system to liquid flow The minimum air pressure used for testing should be at least equal to the maximum rated pressure of t...

Page 13: ...he circuit breaker located on the rear panel 6 The CLF5000 PLL regulates delivered power based upon the setpoint selected by the front panel power control knob 7 The front panel digital meter and selector switch shows power level setpoint actual delivered power output frequency and reflected power 8 An overtemp condition due to lack of coolant flow or high coolant temperature will automatically di...

Page 14: ...hese four power amplifiers are combined in parallel and matched to 50 ohms through a 6 pole low pass filter Control signals are obtained from the output signal as it passes through the power monitor board to the RF output connector The front panel CLF Controller monitors the user input from either the front panel or rear connector and monitors the control signals from the RF output power monitor P...

Page 15: ...mited by reducing setpoint at summing junction R24 R32 The over temperature circuit also disables RF output and stays latched until the RF enable signal from either front panel toggle or rear panel Pins 17 and 4 is turned off The output frequency of the pulse width modulator U1 is monitored by a frequency to voltage converter U8 The circuit is calibrated by pot R95 Four way meter switch S2C enable...

Page 16: ...tage taps off the output line which are multiplied with a four quadrant multiplier U1 and buffered with U3A Reflected power is derived by summing a voltage tap with a current tap which is 180 degrees out of phase with the voltage tap This summed voltage is then squared with four quadrant multiplier U2 and buffered with U3B Forward power is derived by summing the delivered and reflected output sign...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ......

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ......

Reviews: