3.3.5 Combined Setpoints

Press the button when the proper setpoints group is chosen (e.g. ProcessControl)

Use arrows ↑ or ↓ to go to a certain set-point (e.g. PeakAutS/S del) and press Enter button, see picture

below:

Use ↑ or ↓ buttons to select the number, → or ← for the next position or Go Up/Go Down context buttons

and press Enter button.

3.3.6 Unauthorized access message

Setpoints can be locked for unauthorized edit. If a user does not have permission to edit certain setpoints,

"Access Denied" pop-up message is displayed (see picture below).

3.4 AlarmList Screen

On AlarmList screen you can see and work with alarms. When an error occurs, a new alarm appears in the

AlarmList screen, exclamation mark starts blinking on the measurement screens. A small alarm icon is placed

also to heading to be visible in all screens of IV5 including newly generated screens from Screen editor or by

adding new modules in configuration. See picture below:

Summary of Contents for InteliVision 5

Page 1: ...e 7 Czech Republic Tel 420 246 012 111 E mail info comap control com www comap control com Global Guide InteliVision 5 5 7 Display Unit for ComAp controllers SW version 1 9 0 1 Document information 4 2 Installation and wiring 9 3 Graphical User Interface 15 5 Technical data 44 6 List of possible events 45 ...

Page 2: ...2 How to Connect InteliVision 5 to IS NTx BB 10 2 2 3 Terminating resistor 11 2 3 Direct communication between InteliVision 5 and IG IS NT BB controllers 11 2 3 1 Option A 13 2 3 2 Option C 13 2 3 3 Option D 14 3 Graphical User Interface 15 3 1 Front panel 15 3 1 1 LED and Buttons 16 3 1 2 Navigation Buttons 16 3 1 3 Context Buttons 17 3 1 4 Control Buttons 17 3 2 Metering Screens 18 3 3 Setpoints...

Page 3: ...t keys buttons 33 3 7 2 Support of TIER 4 Final standard 34 3 7 3 Change of all label colour 34 4 Quick Help 35 4 1 How to Connect InteliVision 5 to IGS NT 35 4 2 How many InteliVision 5 can be used 36 4 3 Communication Error 36 4 4 How to View a Controller Status 37 4 5 How to View a Breaker Status 37 4 6 How to Control Circuits Breakers 38 4 7 How to Change a Gen set Mode 38 4 8 How to Log in 39...

Page 4: ...ly design of InteliVision 5 introduce the valuable solution for every day usage where more information on the screen and display size is preferred alternative The same cut out across all Comaps products helps InteliVision 5 to be easily used as a replacement of or alternative to IG Display Regardless of the size it can be also used as an alternative to IS Display or InteliVision 8 InteliVision 5 i...

Page 5: ...ot be fully avoided by the below mentioned recommendations and set of measures already performed by ComAp but by following them the cyber attacks can be considerably reduced and thereby to reduce the risk of damage ComAp does not take any responsibility for the actions of persons responsible for cyber attacks nor for any damage caused by the cyber attack However ComAp is prepared to provide techni...

Page 6: ...range power supplies 1 5 Document history Revision number Related sw version Date Author 1 1 9 0 1 12 2017 ComAp 0 1 5 0 2016 ComAp 1 6 Related products Product Description Order code InteliSys Gas Industrial grade controller for gas gen set based CHPs and power generation applications I2GASXXBAB InteliSysNTC Undefined variable Specific BaseBox Premium Parallel Gen set Controller IS NTC BB InteliG...

Page 7: ...er is active Icons at the Bottom of InteliVision 5 Display Mains icon green red voltage frequency are are not in the limits Load icon green grey voltage frequency are in the limits no available power source Gen set icon green grey voltage frequency are in the limits out of the limits or not started Red exclamation mark a new alarm occur in the alarm list Red button breaker failure MCB GCB fail Gre...

Page 8: ...InteliVision 5 Global Guide 8 Measurement screens Setpoints screen Alarm list screen History screen Help Others screen ...

Page 9: ...ntroller 9 2 3 Direct communication between InteliVision 5 and IG IS NT BB controllers 11 6 back to Table of contents 2 1 Terminals and Dimensions InteliVision 5 Cutout 175 x 115 mm 2 2 How to Connect InteliVision 5 to controller InteliVision 5 is possible to connect to controller via NT terminal port or via Direct connection ...

Page 10: ...InteliVision 5 Global Guide 10 2 2 1 How to Connect InteliVision 5 to IG NTx BB 2 2 2 How to Connect InteliVision 5 to IS NTx BB ...

Page 11: ...IG IS NT BB controllers Direct communication enables the usage of converters with constant communication speed in both directions between InteliVision 5 and the controller From version 1 1 1 it is possible to run InteliVision 5 connected to controller RS232 or RS485 port with following setting in the controller ...

Page 12: ...oncrete controllers firmwares where the setpoint RS485 1 conv in the setpoint group Comms is available RS485 1 mode DIRECT RS485 1 conv ENABLED C RS232 2 RS232 2 mode DIRECT RS485 2 conv DISABLED D RS485 2 RS232 2 mode DIRECT RS485 2 conv ENABLED Note RS232 or RS485 1 direct connection can be used They cannot be used simultaneously Only available in IG NTC IS NT BB ...

Page 13: ...InteliVision 5 Global Guide 13 2 3 1 Option A 2 3 2 Option C Analogical to Option A for second RS232 port ...

Page 14: ...InteliVision 5 Global Guide 14 2 3 3 Option D Note Make sure that bias pull up pull down resistors are connected only on one side of the RS485 line 6 back to Installation and wiring ...

Page 15: ...eliVision 5 display unit This manual is intended for everybody who is concerned with operation and controls of the gen set 3 1 Front panel 15 3 2 Metering Screens 18 3 3 Setpoints Screens 21 3 4 AlarmList Screen 24 3 5 History Screen 28 3 6 Help Others Menu 29 3 7 Other features 33 6 back to Table of contents 3 1 Front panel ...

Page 16: ...nter button Context buttons Control or select submenu sub options buttons Control buttons Horn reset Fault reset Stop and Start buttons 3 1 2 Navigation Buttons Menu Movement up Enter Movement down Jump to menu sub menu page or escape from any dialog window Confirms a value or opens a value adjustment within setting dialogs Note To leave the menu use Menu button ...

Page 17: ...cation where MCB is controlled Context buttons may be modified by users to fulfill customer s requirements see chapter User configurable soft keys buttons 3 1 4 Control Buttons Start Starts the gen set Stop Stops the gen set Fault reset Acknowledges faults and alarms active only in Alarm screen Horn reset Deactivates the horn audible alarm Note Start and Stop buttons work in MAN or SEM mode only S...

Page 18: ...p and initialization procedure is done Automatic jump to the home metering screen is performed if there is 15 minutes of inactivity and there are no active and unconfirmed alarms in the controller Arrows or are used for metering screens browsing Metering screens are stored in the controller configuration and can differ by controller type controller firmware version or application ...

Page 19: ...InteliVision 5 Global Guide 19 ...

Page 20: ... for the InteliSys NTC BaseBox controller Other screens with ECU values analogue or binary inputs outputs can follow It depends on the controller configuration Note Use or to scroll the screens Screens could be hidden or the order of the screens could be modified by users ...

Page 21: ...ts groups Setpoints groups depends on the application see Reference Guide of the specific application e g IGS NT SPtM 2 5 reference Guide pdf Setpoints could be presented as a numeric text string or mixed value and they can be changed in the following ways 3 3 1 Numerical Value Change 22 3 3 2 String Selection 22 3 3 3 String Edit 23 3 3 4 Time and Date Edit 23 3 3 5 Combined Setpoints 24 3 3 6 Un...

Page 22: ... and use or buttons to change the value Then use Enter button to confirm new value Note If you set the value out of limit the field will get red colour and the new value is invalid Invalid value cannot be confirmed 3 3 2 String Selection Press the button when the proper setpoints group is chosen e g ProcessControl Use arrows or to go to a certain set point e g Load ctrl PtM and press Enter button ...

Page 23: ...s Enter button see picture below Use or buttons to select the character and buttons for the next position and press Enter button 3 3 4 Time and Date Edit Press the button when the proper setpoints group is chosen e g Date Time Use arrows or to go to a certain set point e g Time and press Enter button see picture below Use buttons to select the number for the next position and press Enter button ...

Page 24: ...access message Setpoints can be locked for unauthorized edit If a user does not have permission to edit certain setpoints Access Denied pop up message is displayed see picture below 3 4 AlarmList Screen On AlarmList screen you can see and work with alarms When an error occurs a new alarm appears in the AlarmList screen exclamation mark starts blinking on the measurement screens A small alarm icon ...

Page 25: ...rms is displayed by YELLOW colour is displayed by RED colour Note When a new alarm appears AlarmList screen is displayed automatically when Main Measurement screen is displayed From different screen AlarmList button has to be used to display AlarmList screen ...

Page 26: ...d exclamation mark will turn off Note When the issue is resolved before Fault Reset button is used the alarm still remains in the AlarmList it will be turned black till you press Fault Reset button 3 4 2 Types of alarms Alarm with asterisk Unacknowledged alarm not confirmed by Fault Reset button Alarm without asterisk Acknowledged alarm confirmed by Fault Reset button Alarm written in colour backg...

Page 27: ...d with analogue value Alarm activated with binary inputs 3 4 3 ECU Alarmlist page InteliDrive controllers family controller have visually separated common and ECU alarms The ECU Alarmlist page is accesible by the button in the user button section ...

Page 28: ...by lines or page or 10x pages Home Jump to the first column when the first column is not on the screen Metering Jump to the last displayed Measurement screen Arrow to left Scroll to the left side Arrow to right Scroll to the right side Note History depends on a controller configuration History is erased when controller configuration is changed and reprogrammed For more information how to change hi...

Page 29: ...uage and press Enter Note InteliVision 5 will reboot when the language is changed This reboot does not affect control unit 3 6 2 User Password When a user is signed into the controller he can choose a user from the list of users every user has got certain rights and then password has to be used To see information how to enter passwords go to How to Enter a Password page 40 and for information how ...

Page 30: ...o to How to Connect InteliVision 5 to IGS NT page 35 3 6 4 ControllerInfo To see information about the control unit see Controller info page On the screen you can find information as See the picture below ID controller string Application used SW version HW version Serial number Password decode HW name ID Chip Dongle SW dongle ...

Page 31: ...CU units see the ECU Modules page See the picture below 3 6 6 Modules Info Modules info is the screen where all connected modules can be seen e g I LB IGS NT E COM etc 3 6 7 InteliVision Info Information about the InteliVision 5 properties can be seen in IV info screen See the picture below ...

Page 32: ...lay awakes from standby mode and backlight of the display is activated Note When Alarmlist contains not confirmed alarms Standby Mode is NOT applied Keyboard and display backlight could be switch on or off based on this set point 3 6 9 Service Screen Context information like a telephone number a name of the service organization and etc could be placed on this screen The Service screen is defined i...

Page 33: ...Reset button each press of a button sets binary signal to 0 Toggle button press set binary signal to 1 or 0 depends on initial value and next press set value to opposite value Initial value can be defined Pulse generator the button generates pulse 1 Genset commands start stop MCB on faultReset etc See example in the picture below The first button is fast link to Generator protection list in Setpoi...

Page 34: ... is added to the configuration in the GenConfig software the Aftertreatment screen is automatically added to the metering screen in the Screen Editor tab Note To fullfill the Tier 4 Final standard there also must be manually configured DEF level and Soat level values to the main metering screen e g DigitLong instrument can be used Some of the controller firmwares already have these values on the m...

Page 35: ...l Adr Controller Adr If NT Terminal as a connection type is selected then second parameter is Terminal Adr indicates which terminal addresses are available green text and which are occupied red text It is possible to connect up to 2 terminals to IG NT BB and up to 3 terminals to IS NT BB controllers When terminal address has to be changed Press Menu button and choose Help Others menu Use or for Co...

Page 36: ...TC BB 4 1 2 3 4 IM NT BB 2 1 2 IG NT C 1 2 IS NT BB 3 2 3 4 IM NT 1 2 For how to set up InteliVision 5 address see How to Connect InteliVision 5 to IGS NT on page 35 4 3 Communication Error Communication error occurs when no control unit is connected to the display or communication is interrupted In that case the following screen appears When the communication between unit and display is fixed the...

Page 37: ...s status is present in all default controller screens Single line diagram defines Mains and gen set condition Status is represented with following colours Represent breaker failure e g MCB fail Represents closed breaker Represents opened breaker Pressing corresponding button results in following actions Open MCB GCB command Open MCB GCB Close MCB GCB command Close MCB GCB Note Mode button and comm...

Page 38: ...s can be controlled in MAN mode only Breaker control button is placed in bottom part of InteliVision 5display See picture bellow 4 7 How to Change a Gen set Mode To Change a Gen set Mode Press Mode context button See the picture below Use or to choose menu item and press Enter ...

Page 39: ... to choose Users Password menu item Use or to go to Users field and press Enter Use or to set the correct user and press Enter See the picture below Note The controller is unlocked only when proper password is inserted When user is log in Green lock is displayed in the right upper corner and appropriate access level is indicated See figure below ...

Page 40: ... in InteliMonitor in Password Menu In default the feature is inactive In the case when Password protection choice is activated and a user inserts wrong password for six times the number of attempts can change according to a new controller SW version to log into the controller the controller is automatically locked for next login When the controller is locked and user tries to login into the contro...

Page 41: ...se or to set the number you need to enter See the picture below 4 11 How to Log out To log out Press Menu button Use or to choose Help Others press Enter Use or to choose Users Password menu item and press Enter Use or to choose Logout and press Enter 4 12 How to Reprogram InteliVision 5 For programming of a new firmware upgrade of fonts and logo download the InteliVision 5 has to be connected to ...

Page 42: ...tab according to desired operation e g Display firmware upgrade Select firmware to be programmed Note It is possible to choose only firmware already imported to GC Press Write to display button and wait until programming is complete Disconnect InteliVision 5 from the controller NT terminal interface It is not possible to program InteliVision 5 through the direct communication interface ...

Page 43: ...ity Hold Menu button until day night mode on the screens appear Press and hold Menu button with or to change brightness intensity Note Brightness setting has priority in this order controller forced brightness InteliVision s 5 analogue input keyboard When the analogue input is used small pictograms in brightness sub menu appears Display backlight could be switched off standby due to Backlight Time...

Page 44: ...65 Operating humidity 85 without condensationIEC EN 60068 2 30 Operating conditions Low Voltage Directive EN 61010 1 95 A1 97 Electromagnetic Compatibility EN 61000 6 3 EN 61000 6 4 EN 61000 6 1 EN 61000 6 2 Vibration EN 60068 2 6 Standard Conformity Dimensions Front panel 245x164mm InteliVision 5 cutout 175x115mm Weight 855g Dimensions and Weight Maximal distance 1000m depends on local conditions...

Page 45: ...mismatch Controller configuration upgrade is necessary Mismatch val states length Error Controller values states mismatch Controller configuration upgrade is necessary Communication Error Controller is detected CAN communication level is not defined correctly Reason of this behavior could be CAN bus line is not terminated properly environment disturbance is present or CAN line is too long Terminal...

Reviews: