InteliNano-NT Plus, SW version 2.0.1.x,
©ComAp – July 2015
49
I11
External Warning 2
If this binary input is activated the red LED above
Stop
button will blink, general warning symbol will
be displayed on LCD’s upper right corner and
symbol will be displayed on event
log with running hours stamp. This alarm is only warning. For more details see
chapter
12 Alarm, Events and History Management.
I12
External Warning 3
If this binary input is activated left red LED above
Stop
button will blink, general warning symbol will
be displayed on LCD’s upper right corner and
symbol will be displayed on event
log with running hours stamp. This alarm is only warning. For more details see
chapter
12 Alarm, Events and History Management.
I13
External Shutdown 1
When this binary input is activated the red LED above
Stop
button will blink, general shutdown
symbol will be displayed on LCD’s upper right corner,
on event log with running hours stamp, and the shutdown procedure will occur. For more details see
12 Alarm, Events and History Management.
C
AUTION
!
This is a software function only.
I14
External Shutdown 2
When this binary input is activated the red LED above
Stop
button will blink, general shutdown
symbol will be displayed on LCD’s upper right corner,
on event log with running hours stamp, and the shutdown procedure will occur. For more details see
12 Alarm, Events and History Management
C
AUTION
!
This is a software function only.
I15
External Shutdown 3
When this binary input is activated the red LED above
Stop
button will blink, general shutdown
symbol will be displayed on LCD’s upper right corner,
on event log with running hours stamp, and the shutdown procedure will occur. For more details see
procedure in chapter
12 Alarm, Events and History Management.
C
AUTION
!
This is a software function only.