InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
400
14.2.1.17
Binary output: Bus fail
Related FW
standard v3.1.0
Description
The output is open if healthy bus voltage is present. It closes with a delay
given by bus protections if bus voltage or frequency gets out of the limits.
14.2.1.18
Binary output: VectorShiftTrp
Related FW
standard v3.1.0
Description
The output closes if the
Vector shift
protection gets active. The output stays
closed for 3s, then opens again.
14.2.1.19
Binary output: Horn
Related FW
standard v3.1.0
Description
The output closes together with the output
. It opens when the output
Horn reset
button is pressed or
elapsed.
14.2.1.20
Binary output: Alarm
Related FW
standard v3.1.0
Description
The output is closed if there is at least one
unconfirmed
alarm in the alarm
list.
N
OTE
:
Some alarm types as e.g.
Off load
,
History record
,
Low power
,
Mains
protection
do not require confirmation, they disappear from the alarm list
automatically when the alarm condition disappears. That means the
Alarm
output is not activated by alarms of these types.