InteliMains 210 Global Guide
431
LBI: N
Related FW
2.0.0
Related applications
MCB, MGCB, BTB
Comm object
184
Description
Binary input has no function. Use this configuration when binary input is not used.
Not Used
back to Logical binary inputs alphabetically
LBI: R
Related FW
2.0.0
Related applications
MCB, MGCB, BTB
Comm object
620
Description
The controller is switched to the AUTO mode (there are four modes OFF / MAN / AUTO / TEST) when this
binary input is closed. When opens controller is switched back to previous mode.
This binary input has the lowest priority from Remote OFF / MAN / AUTO / TEST binary inputs
Remote control priority:
Remote OFF (Highest priority)
Remote TEST
Remote MAN
Remote AUTO (Lowest Priority)
Remote AUTO
back to Logical binary inputs alphabetically
Related FW
2.0.0
Related applications
MCB, MGCB, BTB
Comm object
4
Description
If the input is active, the controller will not accept any actions regarding the system control – e.g. writing of
commands and setpoint changes via remote communication interfaces.
Remote Ctrl Lock