InteliLite4 AMF20 Global Guide
561
back to List of alarms level 2
Alarm Type
SD
Alarmlist message
Sd RPM Measurement Fail
Alarm evaluated
During cranking
Related applications
AMF, MRS
Description
The alarm is issued if the engine speed has not exceeded the
within the
Maximum Cranking Time (page 226)
, although some of
additional running engine indication sources indicate that the engine has started.
Sd RPM Measurement Fail
back to List of alarms level 2
Alarm Type
SD
Alarmlist message
Sd Battery Flat
Alarm evaluated
During cranking
Related applications
AMF, MRS
Description
This alarm will be issued if the controller was reset during cranking of the gen-set.
If this situation occurs, the controller supposes the starting battery is so
exhausted that its voltage drops so low when starter motor is energized that it
causes controller reset.
Sd Battery Flat
back to List of alarms level 2
Alarm Type
SD
Alarmlist message
Sd Start Fail
Alarm evaluated
When the gen-set is being started
Related applications
AMF, MRS
Description
This alarm will be issued after all attempts to start the gen-set have run out but
the Gen-set did not start. The following setpoints are related to this alarm:
adjust the number of attempts
Sd Start Fail
back to List of alarms level 2
Alarm Type
SD
Alarmlist message
SD GCB Fail
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
This alarm will occur when the
input does not match
the expected position given by the
output. It stays
active until the mismatch between the output and feedback persists.
If there was no command issued by the controller and the breaker
(feedback) changes suddenly the position itself, the alarm will be issued
immediately.
Sd GCB Fail