InteliLite4 AMF20 Global Guide
253
Battery Overvoltage
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
Battery Undervoltage (page 252)
.. 40.0 [V]
Default value
36.0 V
Alternative config
NO
Step
0.1 V
Comm object
9587
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Warning threshold for high battery voltage.
Battery <> Voltage Delay
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
0 .. 600 [s]
DefaultFixed
value
5 s
Alternative config
NO
Step
1 s
Comm object
8383
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Delay for
Battery Undervoltage (page 252)
and
Battery Overvoltage (page 253)
protection.
IMPORTANT: This is a fixed parameter, it isn't possible to adjust it in any manner. This
parameter isn't visible either in controller or in PC tools.