InteliLite4 AMF20 Global Guide
252
Transfer Wrn Delay
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
Disabled / 1 .. 600 [s]
Default value
30 s
Alternative config
YES
Step
1 s
Comm object
10685
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Visible only if the logical binary output
is configured
Description
If the controller does not see the fuel increase during fuel transfer within this time alarm
will be displayed and the
will be turned off. Alarm
will be displayed but this alarm becomes immediately inactive and it will be
possible to delete this message by the Fault reset button. If the fault is deleted the controller will initiate the
transfer again.
Subgroup: Battery Protections
Battery Undervoltage
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
8.0 V ..
Battery Overvoltage (page 253)
[V]
Default value
18.0 V
Alternative config
NO
Step
0.1 V
Comm object
8387
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Warning threshold for low battery voltage.