InteliDrive DCU Marine - 3.0.0 Global Guide
171
Setpoint group
SCM unit
Related FW
3.0.0
Range [units]
0 .. 500 [-]
Default value
0
Step
1
Comm object
10907
Related applications
All
Config level
Standard
Setpoint visibility
Always
Description
Conversion ratio (number of pulses for increase by 1) for ID-SCM IMP 2 impulse input / SCM Imp2 value.
Frequency range max. 60 Hz.
Input
Setpoint
Value
RPM1
FreqRate1
SCM Freq1
RPM2
FreqRate2
SCM Freq2
IMP1
TransferRate1
SCM Imp1
IMP2
TransferRate2
SCM Imp2
Example:
To measure actual water flow in liters (or cubic meters) per minute set
FreqRate
= 10 [ ]
when sensor gives 10 pulses per liter (or cubic meters).
Example:
To measure total water consumption in liters (or cubic meters) set
TransferRate
= 100 [ ]
when sensor gives 100 pulses per 1liter (or cubic meter).
TransferRate2
DetCon20
Setpoint group
DetCon20
Related FW
3.0.0
Range [units]
0,0 .. 25,4 [s]
Default value
1,0 s
YES
Step
0,1 s
Comm object
10303
Related applications
All
Config level
Standard
Setpoint visibility
DetCon20 support configured
Description
Delay after load reduction defines delay of timing signal reduction process after knocking level drops below
the
IgnRedLimit
.
DelayLoadRed
Summary of Contents for InteliDrive DCU Marine
Page 29: ...InteliDrive DCU Marine 3 0 0 Global Guide 29 Protection delay and blocking ...
Page 51: ...InteliDrive DCU Marine 3 0 0 Global Guide 51 4 2 2 Electronic engine without redundancy line ...
Page 255: ...InteliDrive DCU Marine 3 0 0 Global Guide 255 Analog inputs from J1939 configuration ...
Page 265: ...InteliDrive DCU Marine 3 0 0 Global Guide 265 Engine Values ...
Page 285: ...InteliDrive DCU Marine 3 0 0 Global Guide 285 6 back to Appendix 6 back to Table of contents ...