InteliDrive DCU Marine - 3.0.0 Global Guide
128
Setpoint group
Engine params
Related FW
3.0.0
Range [units]
0 .. 600 [s]
Default value
0
Step
1
Comm object
8780
Related applications
All
Config level
Standard
Setpoint visibility
Always
Description
This is the time the binary output Prelubrication is active. The controller will activate binary output
Prelubrication for this amount of time, then pause for PrelubrPause, then activate again. This will continue
the entire time the engine is not running. Function is not active in controller OFF mode.
PrelubrTime
Setpoint group
Engine params
Related FW
3.0.0
Range [units]
1 .. 4000 [min]
Default value
1
Step
1
Comm object
8781
Related applications
All
Config level
Standard
Setpoint visibility
Always
Description
Time interval between prelubrication cycles –
.
Note:
To use Prelubrication, configure Binary output Prelubrication at first.
Prelubrication is disabled in controller OFF mode or when PrelubrTime is set to zero.
When engine is running Prelubrication binary output is opened.
Prelubrication starts PrelubrPause after engine stops. Prelubrication starts immediately when:
- controller power supply turns on
- mode changes from OFF to another
- Emergency Stop is released
PrelubrPause
Summary of Contents for InteliDrive DCU Marine
Page 29: ...InteliDrive DCU Marine 3 0 0 Global Guide 29 Protection delay and blocking ...
Page 51: ...InteliDrive DCU Marine 3 0 0 Global Guide 51 4 2 2 Electronic engine without redundancy line ...
Page 255: ...InteliDrive DCU Marine 3 0 0 Global Guide 255 Analog inputs from J1939 configuration ...
Page 265: ...InteliDrive DCU Marine 3 0 0 Global Guide 265 Engine Values ...
Page 285: ...InteliDrive DCU Marine 3 0 0 Global Guide 285 6 back to Appendix 6 back to Table of contents ...