InteliCharger 240 24 Reference Guide

10

See chapter

Battery output wiring diagram (page 7)

for details.

Signal output terminals

Isolated, voltage free, output contacts of mains fail alarm relay (pin 3,4 and 5) are active under AC input fail

conditions. See details in table below.

Mains fail?

Relay output pair

Fail indicator

pin 3–4

pin 3–5

YES

open

closed

– led on

NO

closed

open

– led off

Note:

For better system reliability set up at least 5 s input delay when signal is further processed, for example

by PLC.

Isolated, voltage free, output contacts of battery or charge fail alarm relay (pin 6,7 and 8) are active under low

battery, wrong battery connection, charging fail or battery to be replaced conditions. See details in table below.

Battery or charge fail?

Relay output pair

Fail indicator

pin 6–7

pin 6–8

YES

open

closed

– led on

NO

closed

open

– led off

Note:

In Recovery the Battery or charge fail indicator

is OFF but the Relay is in failure mode (pin 6–8

closed) to indicate a battery with very low voltage.

Max

30 V

DC

, 1 A

60 V

AC

, 1 A

Resistive load (EN 60947-4-1)

Min

5 V

DC

, 1 mA

Min. permissive load.

Relay contact rating

Status indicators

Mains fail indicator.

Battery or charge fail indicator.

Diagnostic indicator.

Charging phase

Diagnostic indicator

Fail indicator

Float

1 blink / 2 s

– led off

Absorption

1 blink / s

– led off

Summary of Contents for InteliCharger 240 24

Page 1: ...public Tel 420 246 012 111 E mail info comap cz www comap cz Global Guide InteliCharger 240 24 Inovative advanced battery charger SW version 1 0 0 1 Document information 3 2 Charger overview 5 3 Wirin...

Page 2: ...ram 7 3 3 Wires parameters 8 4 Charger setup and operation 9 4 1 Front panel description 9 4 2 Detailed description 9 AC input terminal 9 Charging current level 9 Battery output terminal 9 Signal outp...

Page 3: ...itions as applicable ComAp s License Agreement is governed by the Czech Civil Code 89 2012 Col by the Authorship Act 121 2000 Col by international treaties and by other relevant legal documents regula...

Page 4: ...ore details relating to the Ownership Extent of Permitted Reproductions Term of Use of the Documentation and to the Confidentiality rules please review and comply with the ComAp s License Agreement Te...

Page 5: ...as cells in short circuit accidental reverse polarity connection disconnection of the battery These faults can be easily detected and fixed by help of blink code of diagnostic LED during the charger...

Page 6: ...power supply technology High efficiency 88 Protected against short circuit reversed polarity overload and over temperature Signal output terminal voltage free contact for discharged or damaged battery...

Page 7: ...sed bridge corresponding terminals on AC input terminal block see left Note Use appropriate wire cross section See Wires parameters page 8 for details 3 2 Battery output wiring diagram InteliCharger 2...

Page 8: ...ers Use wires with following parameters for all connection type Input Output Signal Solid mm2 Stranded mm2 AWG Torque Nm Stripping length mm 0 2 2 5 0 2 2 5 24 14 0 5 0 6 7 Note The connection is made...

Page 9: ...est function selector 4 2 Detailed description AC input terminal Use 3 wires connection L phase N neutral PE protective earth according to description in chapter AC input wiring diagram page 7 Chargin...

Page 10: ...charge fail alarm relay pin 6 7 and 8 are active under low battery wrong battery connection charging fail or battery to be replaced conditions See details in table below Battery or charge fail Relay o...

Page 11: ...e Jumper position Standard Bulk Absorption Float cell battery voltage Bulk Absorption cell battery voltage in Boost mode Open lead 2 23 V 26 76 V 2 40 V 28 80 V Sealed lead 2 25 V 27 00 V 2 40 V 28 80...

Page 12: ...mplement rapid and automatic charging battery charge optimization flat batteries recovery and real time diagnosis The realtime auto diagnostic system monitors battery and charging proces during the in...

Page 13: ...nnect battery with lower nominal voltage than the charger output voltage Battery might be damaged end of charge when baterry is full charger goes into float charging battery cells in short circuit per...

Page 14: ...to limits Rail mounting The charger module must have a minimum vertical and horizontal distance of 10 cm to the other used DIN rail modules in order to guarantee sufficient auto convection for proper...

Page 15: ...EN 61000 4 3 EN 61000 4 4 EN 61000 4 5 EMC Standards Emission EN 61000 6 4 EN 61000 6 3 EN 61000 3 2 Standards Conformity Safety of Electrical Equipment Machines EN 60204 1 The CE mark in According t...

Page 16: ...echanical specifications Case A rugged aluminum case for DIN rail mounting with top and bottom perforation for auto convention cooling Weight 0 85 kg 1 9 lbs Dimension W H D 112 mm 114 mm 136 mm 4 41...

Page 17: ...of IN 88 Ripple voltage 80 mVPP Output data Short circuit protection Yes Overload protection Yes Overvoltage output protection Yes Reverse battery polarity protection Yes Detection of element in short...

Reviews: