6 Connection
6.1 Recommended CAN/RS485 connection
6.1 Recommended CAN/RS485 connection
6.1.1 CAN bus connection
The bus has to be terminated by 120 Ohm resistors at both ends.
The bus has to be terminated by 120 Ohm resistors at both ends. External units can be connected on the CAN
bus line in any order, but keeping line arrangement (no tails, no star) is necessary.
Standard maximum bus length is 200m for 32C CAN BUS MODE and 900m for 8C CAN BUS MODE (setpoint
in comms setings group).
Shielded cable has to be used, shielding has to be connected to PE on one side (controller side). Recommended
data cables: BELDEN (
For shorter distances (up to 50 m): 3105A Paired - EIA Industrial RS-485 PLTC/CM (1x2 conductors)
For longer distances: 3106A Paired - EIA Industrial RS-485 PLTC/CM (1x2+1 conductors)
In case of surge hazard: 3106A Paired - EIA Industrial RS-485 PLTC/CM (1x2+1 conductors)
Summary of Contents for Inteli Mains NT BaseBox
Page 12: ...IGS NT Communication Guide 12 2 1 IG IS IM NTC BB Communications...
Page 13: ...IGS NT Communication Guide 13 2 2 IG IS IM NTC BB Terminals...
Page 14: ...IGS NT Communication Guide 14 2 3 IG IS IM NTC BB Peripheral modules...
Page 15: ...IGS NT Communication Guide 15 2 4 IG IS IM NTC BB Jumpers settings...
Page 16: ...IGS NT Communication Guide 16 2 5 IG IM NT BB Communication...
Page 17: ...IGS NT Communication Guide 17 2 6 IG IM NT BB Terminal...
Page 18: ...IGS NT Communication Guide 18 2 7 IG IM NT BB Peripheral modules...
Page 19: ...IGS NT Communication Guide 19 2 8 IG IM NT BB Jumper settings...
Page 20: ...IGS NT Communication Guide 20 2 9 IG NT Communications Terminals...
Page 22: ...IGS NT Communication Guide 22 2 11 IM NT Communications Terminals...
Page 23: ...IGS NT Communication Guide 23 2 12 IS NT BB Communications Terminals...
Page 65: ...IGS NT Communication Guide 65...
Page 114: ...IGS NT Communication Guide 114 Image 7 2 InternetBridge NT wired internet connection...