IGS-NT Installation Guide
141
Maximum switching
voltage
36 VDC
36 VDC
36 VDC
20.6.
Analog inputs
Not electrically separated
Number of inputs
3 / 0 / 4 unipolar ( IG-NT(x), IG-NT(x)-BB/ IM-NT
/ IS-NT-BB,IS-NTC-BB )
Resolution
10 bits
Jumper selectable range
V, ohm, mA
Maximal resistance range
2500
Maximal voltage range
5 V
Maximal current range
0
– 20 mA
Input impedance
180
for mA measuring
Input impedance
> 100 k
for V measuring
Resistance measurement tolerance
2 %
2
out of measured value
Voltage measurement tolerance
1 %
1mV out of measured value
Current measurement tolerance
1 %
0,5mA out of measured value
20.7.
D+ function
Max. D+ output current
300 mA
Guaranteed level for signal Charging OK
80% of supply voltage
20.8.
Speed pick-up input
Type of sensor
magnetic pick-up
Minimum input voltage
2 Vpk-pk (from 4 Hz to 4 kHz)
Maximum input voltage
50 Veff
Minimum measured frequency
4 Hz
Maximum measured frequency
10 kHz (min. input voltage 6Vpk-pk)
Frequency measurement tolerance
0,2 %
20.9.
Communication interface
20.9.1.
RS232 interface
Maximal distance
10m
Speed
up to 57.6kBd
20.9.2.
RS485 interface
Maximal distance
1000m
Speed
up to 57.6kBd