ID-FLX Lite & Telecom Global Guide
55
5.15 Functions
5.15.1 Engine operation states
Engine state
Meaning
Init
Auto test during controller power on
Not ready
Engine is not ready to start
Prestart
sequence in process, Prestart output is closed
Cranking
Engine is cranking
Pause
Pause between start attempts
Starting
Starting speed is reached and the
is running
Running
Engine is running
Stop
Stop
Shutdown
Shut-down alarm activated
Ready
Engine is ready to run
Cooling
Engine is cooling before stop
EmergMan
Emergency Manual engine operation
AfterCool
Engine after cooling - Cooling Pump output is closed
5.15.2 OFF mode
No start of the engine is possible. Outputs STARTER and FUEL SOLENOID are not energized. No reaction if
START, STOP buttons are pressed.
5.15.3 MAN mode
START – starts the engine.
STOP – stops the engine.
Note:
The engine can run without load unlimited time.
The controller does not automatically stop the running engine in MAN mode.
The controller does not start the engine when binary input REM START/STOP is closed.
5.15.4 Start-stop sequence (simplified)
MODE = MAN (Engine start/stop request is given by pressing buttons START and STOP)
MODE = AUT (Engine start/stop request is given by binary input REM START/STOP)
State
Condition of the transition
Action
Next state
Ready
Start request
PRESTART on
Prestart time counter
started
Prestart
RPM >2 or Oil pressure detected or D+ is active
Stop (Stop fail)
OFF mode selected or Shut down alarm active
Not Ready
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...