ID-FLX Lite & Telecom Global Guide
112
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
0 .. 600 [s]
Default value
2
-
Step
1
Comm object
8394
Related applications
Description
Time of the PRESTART output closed prior to the engine start – i.e. before the binary outputs Fuel solenoid
and Starter are closed and opens when Starting RPM speed is reached. Set to zero if you want to leave the
output PRESTART opened.
Prestart time
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
0 .. 600 [s]
Default value
0
-
Step
1
Comm object
11836
Related applications
N/A
Description
This setpoint is used for setting of timer for deactivation of
.
Preglow time
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
-600 ..
[°C]
Default value
0 °C
-
Step
1 °C
Comm object
15985
Related applications
N/A
Description
Defines the temperature, at which the LBO Preheat activate of the longest time prior to engine start. See
description of
.
PreheatTemp1