ID-FLX Lite & Telecom Global Guide
200
Related FW
2.5.0
Related applications
Comm object
1247
Description
Output closes together with
and opens after the engine is stopped.
Stopped engine conditions: RPM = 0,
,
(if enabled).
Air valves
Related FW
2.5.0
Related applications
Comm object
2
Description
The output closes if:
Any warning, cooldown or shutdown comes up or
The engine malfunctions
The output opens if
FAULT RESET is pressed
The output closes again if a new fault comes up.
Alarm
Related FW
2.5.0
Related applications
Comm object
1
Description
The output closes if:
Any warning or shutdown comes up or
The engine malfunctions
The output opens if:
FAULT RESET is pressed or
HORN RESET is pressed or
Max time of LBO HORN is exceeded (Horn timeout)
The output closes again if a new fault comes up.
Horn
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...