Accessory Modules for IL-NT, IC-NT, IA-NT and ID-Lite Global Guide
51
4.13 IC-NT-CT-BIO7
4.13.1 Description
IC-NT CT-BIO7 is equipped with one AC current (CT) measuring input and up to 7 binary inputs or outputs In
LiteEdit PC tool (version 4.4 and higher) it is possible to easily choose and configure particular I/O will be
binary input or output.
Note:
Current measuring input is intended to measure one phase (AC) current of mains and to limit
Export/Import to/from mains to zero value during parallel to mains operation. This is case of SPtM
application, so current input of IC-NT CT-BIO7 module is useful for SPtM controllers only.
4.13.2 Connectors
INPUTS1
7 mixed binary inputs or
outputs
OUTPUTS1
4.13.3 Address and jumper setting
There is no possibility to set address of module.
4.13.4 Others information
This module is configurable in LiteEdit – Modify configuration – Extension plug-in modules – IL-NT-BIO8.