Accessory Modules for IL-NT, IC-NT, IA-NT and ID-Lite Global Guide
13
USB interface allows only local communication (modbus is not implemented in this interface!).
Jumper
Description
State
P1
CAN terminating resistor
Opened – not connect
P2
RS485 terminating resistor
Opened – not connect
P3
RS232 or RS485
1–2 – active RS232
P8
USB enable/disable
Opened – disabled
P13
Modbus rate
Opened
P14
Modbus rate
Opened – 9600 bps
P15
HW or SW modem control
Opened – HW control
P16
ComAp or Modbus
Opened – ComAp protoco
P17
ADR1 or ADR2
Opened – ADR1
P18
Direct or Modem
Opened – Direct
Jumper tree
ComAp
DIRECT
RS232/RS485 – selection of serial communication type
ADR1/ADR2 – selection between two available local communication channels
MODEM
HW/SW control – selection between modems with full interface
ADR1/ADR2 – selection between two available modem communication channels; IG/IS-NT
controllers only
Setting RS232/RS485 jumper to RS232 position is obligatory
Modbus (not available at USB port of I-LB+, USB port always works in ComAp mode)
DIRECT
RS232/RS485 – selection of serial communication type
ADR1/ADR2 – selection between two available local communication channels
MODEM
ADR1/ADR2 – selection between two available modem communication channels; IG/IS-NT
controllers only,
Setting HW/SW control has no influence; a modem with HW control is always expected in this
mode
Programming
For programming is necessary to close BOOT jumper. RESET jumper is used to reset the device. Close
jumper to reset the device. For programming is used FlashProg PC tool. Check if jumper P3 is set according
to your communication interface (mostly RS232 – position 1-2).