Coleman PCG4A36 Technical Manual Download Page 12

5564041-CTG-A-1018

12

Johnson Controls Unitary Products

AIRFLOW PERFORMANCE - SIDE DUCT APPLICATION 

Model

Motor Speed

External Static Pressure (Inches WC)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

1.0

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

SCFM

36050

Low (1)

1003

952

904

851

790

730

674

633

551

Low/Medium (2)

1180

1133

1085

1042

995

942

889

834

724

Medium (3)

1259

1209

1166

1126

1084

1032

980

928

824

Medium/High (4)

1314

1271

1229

1186

1144

1097

1049

998

896

High (5)

1506

1471

1403

1389

1345

1305

1262

1216

1124

36075

Low (1)

1225

1174

1131

1090

1046

993

941

888

782

Low/Medium (2)

1259

1209

1166

1126

1084

1032

980

928

824

Medium (3)

1314

1271

1229

1186

1144

1097

1049

998

896

Medium/High (4)

1348

1306

1259

1222

1179

1133

1086

1036

936

High (5)

1506

1471

1403

1389

1345

1305

1262

1216

1124

36100

Low (1)

1342

1302

1260

1217

1178

1134

1082

1034

938

Low/Medium (2)

1425

1368

1332

1293

1251

1208

1163

1113

1013

Medium (3)

1554

1503

1465

1423

1386

1346

1302

1257

1167

Medium/High (4)

1658

1599

1588

1530

1495

1454

1414

1373

1291

High (5)

1966

1914

1862

1810

1757

1705

1653

1600

1496

42075

Low (1)

1315

1266

1229

1194

1156

1117

1080

1036

948

Low/Medium (2)

1436

1382

1342

1304

1262

1220

1179

1131

1035

Medium (3)

1458

1406

1365

1327

1286

1244

1203

1155

1059

Medium/High (4)

1573

1523

1484

1445

1408

1367

1327

1279

1183

High (5)

1966

1914

1862

1810

1757

1705

1653

1600

1496

42100

Low (1)

1436

1382

1342

1304

1262

1220

1179

1131

1035

Low/Medium (2)

1544

1492

1455

1416

1376

1336

1294

1248

1156

Medium (3)

1573

1523

1484

1445

1408

1367

1327

1279

1183

Medium/High (4)

1681

1640

1599

1557

1517

1478

1436

1393

1307

High (5)

1935

1887

1834

1788

1743

1701

1651

1591

1471

48065

Low (1)

1046

1009

980

946

915

878

844

779

649

Low/Medium (2)

1295

1250

1213

1172

1133

1087

1045

964

802

Medium (3)

1620

1564

1517

1466

1418

1360

1308

1206

1002

Medium/High (4)

1798

1722

1669

1620

1572

1527

1480

1413

1280

High (5)

2146

2085

2025

1960

1872

1862

1798

1735

1609

48100

Low (1)

1620

1564

1517

1466

1418

1360

1308

1206

1002

Low/Medium (2)

1694

1630

1580

1530

1482

1430

1380

1292

1116

Medium (3)

1798

1722

1669

1620

1572

1527

1480

1413

1280

Medium/High (4)

1835

1758

1703

1653

1604

1558

1511

1442

1304

High (5)

2146

2085

2025

1960

1872

1862

1798

1735

1609

48125

Low (1)

1620

1564

1517

1466

1418

1360

1308

1206

1002

Low/Medium (2)

1798

1722

1669

1620

1572

1527

1480

1413

1280

Medium (3)

1922

1863

1804

1754

1724

1658

1612

1559

1453

Medium/High (4)

2001

1952

1890

1839

1820

1742

1696

1651

1561

High (5)

2146

2085

2025

1960

1872

1862

1798

1735

1609

60065

Low (1)

1073

1043

1009

988

963

941

917

892

842

Low/Medium (2)

1329

1292

1250

1223

1192

1165

1136

1105

1043

Medium (3)

2054

1998

1934

1890

1843

1801

1757

1710

1616

Medium/High (4)

2195

2144

2098

2049

2003

1955

1883

1868

1838

High (5)

2445

2388

2306

2293

2235

2178

2129

2077

1973

60100

Low (1)

1730

1682

1628

1592

1552

1517

1479

1439

1359

Low/Medium (2)

1858

1807

1749

1710

1667

1629

1589

1546

1460

Medium (3)

2054

1998

1934

1890

1843

1801

1757

1710

1616

Medium/High (4)

2195

2144

2098

2049

2003

1955

1883

1868

1838

High (5)

2445

2388

2306

2293

2235

2178

2129

2077

1973

Continued on next page.

Summary of Contents for PCG4A36

Page 1: ...computerized process system are used to insure product quality Refrigerant charge and component part numbers are verified via computers during assembly Vital run test statistics such as system pressure motor cur rents air velocity and temperature unit vibration and gas system safeties are monitored and recorded by the system to insure unit performance Equal size side supply and return duct connect...

Page 2: ...pressor compartment The controls are mounted to allow the separate access panel to be removed for trouble shooting and maintenance without affecting the normal system operating pressures All wiring internal to the unit is color number coded Protected Compressor The compressor is internally pro tected against high pressure and temperature This is accomplished by the simultaneous operation of high p...

Page 3: ...g Capacity 24 Nominal Capacity etc 9 Revision Level A original release B second release Examples PCG4B421002X1A is a packaged A C with gas heat 14 SEER 3 1 2 ton large cabinet three stage heat 100 000 BTU gas heat 230 volt three phase low NOx model first generation first release COMPONENT LOCATION FAN MOTOR OUTDOOR FAN COIL GUARD PANEL OUTDOOR COIL Behind Panel CONTROL BOARD TRANSFORMER HIGH VOLTA...

Page 4: ...rough 50 of outdoor air field supplied Closes on power loss includes hood and screen assembly Loss of Charge Switch S1 2LC00024 Kit provides Loss of Charge sensor and wiring to provide safe shutdown of compressor Rectangle to Round Horizontal Adapter S1 1AK0110 S1 1AK0111 Kit includes one supply and one return air rectangle to round duct adapter Adapters are preformed and designed to fit over curr...

Page 5: ... Fan shall be direct drive design Fan wheel shall be double inlet type with forward curved blades dynamically balanced to operate smoothly throughout the entire range of operation Airflow design shall be constant air volume Bearings shall be sealed and permanently lubricated for longer life and no maintenance Fan assembly shall be a slide out design for easy removal and cleaning Indoor blower moto...

Page 6: ...perating WT lbs 394 401 405 441 443 460 468 473 477 481 488 Compressors Type Scroll Scroll Scroll Scroll Outdoor Coil Data Face area Sq Ft 15 1 16 9 19 5 21 5 Rows 2 2 2 2 Fins per inch 22 22 22 22 Tube diameter 3 8 3 8 3 8 3 8 Circuitry Type Interlaced Interlaced Interlaced Interlaced Indoor Coil Data Face area Sq Ft 4 6 4 6 6 3 6 3 Rows 3 3 3 3 Fins per inch 16 16 16 16 Tube diameter 3 8 3 8 3 8...

Page 7: ...6 8 24 4 20 2 20 9 16 2 28 5 26 9 22 1 23 1 17 4 K W 3 30 3 39 3 39 3 41 3 42 3 25 3 47 3 46 3 48 3 49 3 21 3 55 3 54 3 55 3 57 COOLING PERFORMANCE DATA 3 5 TON PACKAGED UNIT MODEL NO PCG4A42 CONDENSER ENTERING AIR TEMPERATURE ID CFM 1200 1400 1600 IDDB 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 IDWB 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72 55 45 T C 43 7 46 9 46 8 51 8 57 3 46 5 48 6 48 5 5...

Page 8: ...24 5 29 0 26 0 28 8 20 9 24 6 29 6 25 6 31 0 21 9 K W 5 30 5 29 5 30 5 33 5 35 5 37 5 36 5 36 5 39 5 41 5 44 5 42 5 42 5 45 5 47 COOLING PERFORMANCE DATA 5 TON PACKAGED UNIT MODEL NO PCG4B60 CONDENSER ENTERING AIR TEMPERATURE ID CFM 1600 1800 2000 IDDB 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 IDWB 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72 55 45 T C 68 0 69 1 68 1 73 0 79 5 70 4 70 4 69 3 74...

Page 9: ...ed space and recirculate Direction Distance in Direction Distance in Top3 3 Units must be installed outdoors Over hanging structure or shrubs should not obstruct condenser air discharge outlet 36 Power Entry Right Side 36 Side Opposite Ducts 36 Left Side 24 Duct Panel 0 Bottom4 4 Units may be installed on combustible floors made from class A B or C roof covering materials 1 92 7 23 1 1 92 7 23 1 1...

Page 10: ...th AHRI Standard 270 Octave Band Centerline Frequency Hz 125 250 500 1000 2000 4000 8000 A36 74 58 5 61 8 65 4 66 5 60 7 54 8 49 8 A42 74 63 5 63 9 62 3 65 0 64 0 54 1 46 6 B48 74 63 5 63 9 62 3 65 0 64 0 54 1 46 6 B60 76 72 3 65 0 63 9 64 0 60 0 55 5 49 0 ELECTRICAL DATA Model Voltage Compressor OD Fan Motor Supply Blower Motor MCA1 Amps Max Fuse2 Breaker3 Size Amps RLA LRA MCC FLA FLA 36050 3607...

Page 11: ... 406 401 28 15 135 115 103 74 36100 410 405 28 15 139 113 99 80 42075 446 441 28 15 145 112 99 85 42100 448 443 28 15 148 110 96 89 48065 465 460 28 15 189 116 93 117 48100 473 468 28 15 169 139 115 100 48125 478 473 28 15 164 145 124 95 60065 482 477 29 15 174 142 124 92 60100 486 481 28 15 177 140 117 102 60125 493 488 27 15 151 167 141 84 X CENTER OF GRAVITY FRONT OF UNIT Y D C B A A0295 001 TG...

Page 12: ...55 1416 1376 1336 1294 1248 1156 Medium 3 1573 1523 1484 1445 1408 1367 1327 1279 1183 Medium High 4 1681 1640 1599 1557 1517 1478 1436 1393 1307 High 5 1935 1887 1834 1788 1743 1701 1651 1591 1471 48065 Low 1 1046 1009 980 946 915 878 844 779 649 Low Medium 2 1295 1250 1213 1172 1133 1087 1045 964 802 Medium 3 1620 1564 1517 1466 1418 1360 1308 1206 1002 Medium High 4 1798 1722 1669 1620 1572 152...

Page 13: ... 1146 1103 1069 1030 977 912 781 Low Medium 2 1270 1225 1189 1140 1098 1046 1008 960 866 Medium 3 1317 1286 1245 1198 1151 1110 1064 1024 943 Medium High 4 1358 1317 1275 1238 1197 1148 1105 1057 961 High 5 1517 1475 1447 1400 1357 1318 1275 1232 1146 36100 Low 1 1340 1299 1264 1224 1182 1182 1097 1049 953 Low Medium 2 1409 1368 1334 1291 1253 1201 1173 1128 1038 Medium 3 1527 1492 1470 1419 1385 ...

Page 14: ...65 Low 1 1026 999 989 950 907 907 886 862 816 Low Medium 2 1263 1230 1192 1165 1167 1101 1099 1071 1015 Medium 3 1987 1933 1861 1817 1820 1715 1725 1651 1504 Medium High 4 2114 2050 2047 1974 1899 1889 1920 1866 1758 High 5 2369 2308 2249 2183 2126 2088 2034 1990 1902 60100 Low 1 1655 1612 1596 1531 1461 1462 1429 1391 1316 Low Medium 2 1766 1720 1667 1629 1632 1539 1537 1498 1421 Medium 3 1987 19...

Page 15: ... 06 0 04 0 06 1600 0 07 0 04 0 07 1700 0 07 0 04 0 08 1800 0 08 0 04 0 09 1900 0 09 0 05 0 10 2000 0 09 0 05 0 11 B48 4 0 1100 0 02 0 02 0 04 1200 0 03 0 02 0 04 1300 0 04 0 02 0 05 1400 0 05 0 03 0 05 1500 0 06 0 04 0 06 1600 0 07 0 04 0 07 1700 0 07 0 04 0 08 1800 0 08 0 04 0 09 1900 0 09 0 05 0 10 2000 0 09 0 05 0 11 B60 5 0 1100 0 02 0 02 0 04 1200 0 03 0 02 0 04 1300 0 04 0 02 0 05 1400 0 05 ...

Page 16: ...ON REAR DUCT ROOF CURB INSTALLATION BOTTOM DUCT SLAB ON GROUND INSTALLATION A032 UNIT TYPICAL SLAB ON GROUND INSTALLATION A0325 001 SUPPLY AIR DUCT TO POWER SUPPLY RETURN AIR DUCT FIELD SUPPLIED DISCONNECT SWITCH CONTROL WIRING TO INDOOR THERMOSTAT TO GAS SUPPLY LINE MANUAL GAS SHUTOFF VAVLE CONDENSATE DRAIN ...

Page 17: ...oducts 17 UNIT TYPICAL ROOF CURB INSTALLATION SUPPLY AIR DUCT TO POWER SUPPLY RETURN AIR DUCT FIELD SUPPLIED DISCONNECT SWITCH CONTROL WIRING TO INDOOR THERMOSTAT TO GAS SUPPLY LINE MANUAL GAS SHUTOFF VAVLE ROOF CURB ROOF CONDENSATE DRAIN A0326 001 ...

Page 18: ... change without notice Published in U S A 5564041 CTG A 1018 Copyright 2018 by Johnson Controls Inc All rights reserved Supersedes 5006144 CTG F 1017 York International Corp 5005 York Drive Norman OK 73069 NOTES ...

Reviews: