![Coleman PCG4A36 Technical Manual Download Page 10](http://html1.mh-extra.com/html/coleman/pcg4a36/pcg4a36_technical-manual_2635573010.webp)
5564041-CTG-A-1018
10
Johnson Controls Unitary Products
INDOOR BLOWER SPECIFICATIONS
Model
Motor
HP
RPM
EFF.
SF
Frame
24050
1/3
Variable
0.8
1.0
48
24075
1/2
Variable
0.8
1.0
48
30050
1/3
Variable
0.8
1.0
48
30075
1/2
Variable
0.8
1.0
48
36050
1/2
Variable
0.8
1.0
48
36075
1/2
Variable
0.8
1.0
48
36100
3/4
Variable
0.8
1.0
48
42075
3/4
Variable
0.8
1.0
48
42100
3/4
Variable
0.8
1.0
48
48065
3/4
Variable
0.8
1.0
48
48100
3/4
Variable
0.8
1.0
48
48125
3/4
Variable
0.8
1.0
48
60065
1
Variable
0.8
1.0
48
60100
1
Variable
0.8
1.0
48
60125
1
Variable
0.8
1.0
48
SOUND PERFORMANCE
Model
(Tons)
Sound Rating
1
dB (A)
1. Rated in accordance with AHRI Standard 270.
Octave Band Centerline Frequency (Hz)
125
250
500
1000
2000
4000
8000
A36
74
58.5
61.8
65.4
66.5
60.7
54.8
49.8
A42
74
63.5
63.9
62.3
65.0
64.0
54.1
46.6
B48
74
63.5
63.9
62.3
65.0
64.0
54.1
46.6
B60
76
72.3
65.0
63.9
64.0
60.0
55.5
49.0
ELECTRICAL DATA
Model
Voltage
Compressor
OD Fan
Motor
Supply
Blower Motor
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA
LRA
MCC
FLA
FLA
36050, 36075
208/230-3-60
10.4
73.0
16.3
1.3
3.8
18.1
25
36100
208/230-3-60
10.4
73.0
16.3
1.3
5.4
18.1
25
42075, 42100
208/230-3-60
13.5
88.0
21.1
1.3
5.4
23.6
35
48065, 48100, 48125
208/230-3-60
13.7
83.1
21.4
1.7
5.4
24.2
35
60065, 60100, 60125
208/230-3-60
16.0
110.0
24.9
1.7
7.0
28.7
40
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.