background image

CAUTION: Fan/limit control location is critical in the
P*DHX12F08001 horizontal positions. To operate ef-
fectively as a high limit control, the fan / limit control
must be installed in the upper position. See Figure 3.

CHIMNEY VENTING

The flue pipe should be as short as possible with horizontal
pipes sloping upward toward the chimney at a rate of one quar-
ter inch to the foot. The flue pipe should not be smaller in cross
sectional area than the flue collar on the furnace.

The flue pipe should connect to the chimney such that the flue
pipe extends into, and terminates flush with the inside surface
of the chimney liner. Seal the joint between the pipe and the lin-
ing.

The chimney outlet should be at least two feet above the high-
est point of a peaked roof. All unused chimney openings should
be closed.

Chimneys must conform to local, provincial or state codes, or in
the absence of local regulations, to the requirements of NFPA
2.11 (latest edition) Chimney, Fireplaces, Vents and Solid Fuel
Burning Appliances 
(in Canada CSA B139)..

NOTE: All furnace models are approved for use with
Type L vent or equivalent.

CAUTION: The furnace must be connected to a flue
having sufficient draft at all times to ensure safe and
proper operation of the appliance.

NOTE: The recommended flue draft pressure is --
0.02 in. W.C. (as measured upstream of the baromet-
ric draft regulator).

The flue pipe must not pass through any floor or ceiling, but
may pass through a wall where suitable fire protection provi-
sions have been installed. Refer to the latest edition of ANSI
NFPA 31 (in the United States, or CAN/CSA B--139 in Canada)
for regulations governing the installation of oil burning equip-
ment.

See Table 4 for burner set-up.

BAROMETRIC DAMPER CONTROL

This device must be used with all chimney and Type L vent sys-
tems. This control (or draft regulator) automatically maintains a
constant negative pressure in the furnace to obtain maximum
efficiency. It ensures that proper pressures are not exceeded.

If the chimney does not develop sufficient draft, the draft control
cannot function properly. The draft regulator, when installed
should be in the same room or enclosure as the furnace and
should not interfere with the combustion air supplied to the
burner.

The control should also be located near the furnace flue outlet
and installed according to the instructions supplied with the
regulator. The flue outlet pressure (measured between the fur-
nace and draft regulator) should be set to --0.02 in. w.c.

FAN AND LIMIT CONTROL

Upflow & Lowboy Models
The L6064A temperature sensitive fan switch is actuated by a
helical bi--metal sensing element enclosed in a metal guard,
and controls the circulating air blower. This provides a delay
between the burner ignition and blower start up to eliminate ex-
cessive flow of cold air when the blower comes on. Blower
shutdown is also delayed to remove any residual heat from the
heat exchanger and improve the annual efficiency of the fur-
nace. Fan settings of 120

°

F to 130

°

F (50

°

C to 55

°

C) and fan

settings of 90

°

F to 100

°

F (32

°

C to 37

°

C) will usually be satis-

factory.

Downflow /Horizontal Models
The L4064W temperature sensitive fan switch contains a
heater--wrapped bi--metal to actuate the fan switch independ-
ent of the temperature at the helical sensing element. The time
from ignition, to the blower on function is approximately 30 sec-
onds. If after 1 minute, the blower has not come on, replace-
ment of the control may be necessary. The blower shutdown is
the same as noted for the L6064A control.

The limit switch performs a safety function and breaks power to
the oil burner primary control, which shuts off the burner if the
furnace over--heats. The limit control is thermally operated and
automatically resets. The limit control is factory installed, pre--
set and is not adjustable.

The limit control and fan control are incorporated in the same
housing and are operated by the same thermal element.

The downflow furnace utilizes an additional auxiliary limit con-
trol which is an automatic reset type.

ELECTRICAL CONNECTIONS

The furnace is listed by the Canadian Standards Association
under the NRTL (North American) Standard. It is factory wired
and requires minimal field wiring. All field wiring should con-
form to the following standards or by local codes, where they
prevail and by In the United States, refer to the National Fire
Protection Association NFPA--70, National Electrical Code
(latest edition), or in Canada, CAN/CSA C22.1 Canadian Elec-
trical Code, Part 1, and with local codes and regulations.

The furnace should be wired to a separate and dedicated cir-
cuit in the main electrical panel; however, accessory equip-
ment such as electronic air cleaners and humidifiers may be
included on the furnace circuit. Although a suitably located cir-
cuit breaker can be used as a service switch, a separate serv-
ice switch is advisable. The service switch is necessary if
reaching the circuit breaker involves becoming close to the fur-
nace, or if the furnace is located between the circuit breaker
and the means of entry to the furnace room.

6

Unitary Products Group

035-14289-000 Rev. A (0701)

AIR FLOW

FAN & LIMIT LOCATION

AIR FLOW

LEFT HORIZONTAL APPLICATION

RIGHT HORIZONTAL APPLICATION

FAN & LIMIT LOCATION

FIGURE 3 - HORIZONTAL APPLICATION

FAN/LIMIT LOCATION

Summary of Contents for P*DHX12F0801

Page 1: ...ency or the oil supplier P HB UPFLOW INSTALLATION INSTRUCTION OIL FIRED WARM AIR FURNACES Supersedes 035 14289 000 A 300 035 14289 000 A 1101 CAUTION THIS PRODUCT MUST BE INSTALLED IN STRICT COM PLIANCE WITH THE ENCLOSED INSTALLATION IN STRUCTIONS AND ANY APPLICABLE LOCAL STATE AND NATIONAL CODES INCLUDING BUT NOT LIM ITED TO BUILDING ELECTRICAL AND ME CHANICAL CODES WARNING IMPROPER INSTALLATION ...

Page 2: ...ns provided the results obtained are in substantial agreement with and not less than those obtained using the procedure described in the manual LOCATION OF UNIT The furnace should be located such that the flue connection to the chimney is short direct and consists of as few elbows as possible When possible the unit should be centralized with re spect to the supply and return air duct work A centra...

Page 3: ...6F12001 are factory shipped for downflow installation Downflow If the furnace is to be installed in a downflow application a com bustible floor base must be used either 1CB0312 or 1CB0316 Refer to Figure 1 Horizontal For applying the furnace in a horizontal left or horizontal right application follow these steps 1 Rotate the furnace 90 degrees to the desired position 2 Remove three nuts and washer...

Page 4: ...SUPPLY AIR RETURN AIR P DHX12F08001 51 22 31 1 4 19 19 18 18 5 P DHX16F12001 62 22 1 4 22 1 4 20 1 2 20 1 2 18 18 6 LOWBOY SUPPLY AIR RETURN AIR P LBX12F08001 31 22 43 20 1 2 18 5 8 20 1 2 18 5 8 5 REAR P LBX16F12001 41 22 52 1 2 20 1 2 18 5 8 20 1 2 18 5 8 6 REAR P LBX16F14501 41 22 52 1 2 20 1 2 18 5 8 20 1 2 18 5 8 6 REAR P LBX20F19001 56 26 49 24 22 24 22 7 REAR TABLE 2 UNIT DIMENSIONS C E K H...

Page 5: ... 2 1 2 3 1200 P DHX16F12001 140 120 1 0 80 1 1593 12 0 15 14 11 x 10 1 2 1 20 x 20 3 3 1 2 4 1600 LOWBOY P LBX12F08001 91 80 65 85 1 1717 12 0 15 14 12 x 9 1 2 1 20 x 20 2 2 1 2 3 3 1 2 4 1200 P LBX16F12001 140 120 1 0 83 4 1585 12 0 15 14 12 x12 1 2 1 20 x 25 3 3 1 2 4 1600 P LBX16F14501 168 145 1 20 83 5 1585 12 0 15 14 12 x 12 1 2 1 20 x 25 3 3 1 2 4 1600 P LBX20F19001 231 190 1 65 78 0 2135 12...

Page 6: ...emperature sensitive fan switch is actuated by a helical bi metal sensing element enclosed in a metal guard and controls the circulating air blower This provides a delay between the burner ignition and blower start up to eliminate ex cessive flow of cold air when the blower comes on Blower shutdown is also delayed to remove any residual heat from the heat exchanger and improve the annual efficienc...

Page 7: ...e lift on a single line system is 8 ft Lift should be measured from the bottom outlet of the tank to the inlet of the burner Sizing a single line system is complex because of the difficulty estimating the pressure drop through each fitting bend and component in the line In general keep single line systems short as possible If the furnace is to be installed in a sus pended position a two pipe syste...

Page 8: ... amping of the direct drive blower motor Selecting a lower blower speed may cor rect this problem Direct drive blower speeds are adjusted by changing the hot wires to the motor winding connections Please refer to wiring diagram on Page 12 or the wiring diagram label affixed to the furnace THE NEUTRAL WIRE normally the white wire IS NEVER MOVED TO ADJUST THE BLOWER SPEED It is possible and acceptab...

Page 9: ...nd debris with a wire han dled brush and an industrial vacuum cleaner Before replacing the clean out covers inspect the gaskets If the gaskets are broken remove the remnants and replace with new gaskets Snug the cleanout covers DO NOT OVER TORQUE THE CLEAN OUT NUTS Replace the inner front panel clean out covers NOTE A radiator clean out assembly inadvertently dropped into the interior of the furna...

Page 10: ...URNER SET UP The burner air supply is adjusted to maintain the fuel to air ratio to obtain ideal combustion conditions Alack of air causes soft and sooty flames resulting in soot build up throughout the heat exchanger passages Excess combustion air causes a bright roaring fire and high stack temperatures resulting in poor fuel efficiency Preparations Drill a 1 4 test port in the venting ideally at...

Page 11: ...e flue gases are above the range the blower may require speeding up Stack temperature varies directly with the system temperature rise System temperature rise is the difference between the furnace outlet temperature and the furnace inlet temperature as measured in the vicinity of the connection between the plenum take offs and the trunk ducts Typical temperature rise values range between 65 F and ...

Page 12: ...H 1752 1691 1659 1593 1525 MED HIGH 1454 1454 1417 1379 1300 MED LOW 975 944 912 879 844 LOW 631 593 552 515 486 P LBX12F08001 HIGH 1917 1885 1820 1717 1608 MED HIGH 1590 1608 1590 1532 1430 MED LOW 1096 1096 1096 1068 1039 LOW 696 647 692 647 598 P LBX16F12001 P LBX16F14501 HIGH 1810 1740 1675 1585 1480 MED HIGH 1570 1540 1495 1445 1348 MED LOW 1090 1080 1070 1065 1036 LOW 710 700 690 665 614 P L...

Page 13: ...Unitary Products Group 13 035 14289 000 Rev A 0701 WIRING DIAGRAM ALL MODELS ...

Page 14: ...f necessary Ensure that erratic pressure readings are not caused by defective fuel oil lines Air getting into fuel oil lines or fuel oil line dirty clogged or in some manner defective Check oil lines Replace any compression fittings found with high quality flared fittings Check for any signs of oil leaks An oil leak is a potential source of air or contaminants Defective burner motor Check burner m...

Page 15: ...ure Adjust the oil burner combustion air band and draft regulator to gain the highest CO2 possible with a Bacharach No 1 smoke Heat exchanger partially clogged Check for soot build up in heat exchanger flue passages especially in the outer radiator Furnace will not warm home to desired tempera ture Air flow blocked by dirty air filter Clean or replace air filter Thermostat adjustments or location ...

Page 16: ...nge without notice Printed in U S A Copyright by Unitary Products Group 1999 All rights reserved 035 14289 000 A 1101 Code EBY L F Supersedes 035 14289 A 000 300 5005 York Drive Norman OK 73069 Unitary Products Group ...

Reviews: