12 | Repair
68 / 88
Operating instructions CMVpro 125-400 ATEX | Version 1-en
Fault
Possible cause
Fault discovery
Remedy
FC parameter "max.
frequency" set improp-
erly (speed too high,
overheating of electric
motor).
Check FC parameters
_
50].
Adjust parameters ac-
cording to characteris-
tic map in technical
data sheet.
Grinding noise
coming from
the impeller.
Casing too tight.
Check distance and
alignment of ductwork
to fan connection.
Adjust ductwork dis-
tance and connection
(sleeves) appropri-
ately.
Ductwork connected to
fan without sleeves.
Connect ductwork to
fan with sleeves
_
41].
Loose impeller.
Impeller loosened on
motor shaft?
Check and tighten hub
adapter
_
Deposits or foreign ob-
jects between impeller
and inlet cover.
Determine grinding
point.
Check with feeler
gauge.
Remove deposits or
foreign objects
_
62].
Impeller defect.
Visual inspection.
Replace impeller
_
Audible sound
from bearings.
Bearing damage.
Auditory inspection.
Replace motor bear-
ings or exchange mo-
tor
_
End of service life
reached.
Bearing damage due
to electrical discharge
machining (bearing
currents).
Measure voltage be-
tween the motor shaft
and casing of the elec-
tric motor.
Interference suppres-
sion measures with FC
operation; see FC
manufacturer’s guid-
ance. Check EMC
guidelines.
Use current-insulated
roller bearings or ce-
ramic hybrid bearings.
Excessive
leakage at im-
peller hub.
Overpressure opera-
tion of the fan (without
optional hub seal).
Pressure measure-
ment.
Operate fan at nega-
tive pressure.
Install optional hub
seal.
Hub seal worn or de-
fective.
Visual inspection.
Replace sealing
_