Repair | 12
Operating instructions CMVpro 125-400 ATEX | Version 1-en
65 / 88
Fault
Possible cause
Fault discovery
Remedy
Observe minimum dis-
tance between fan
connection and
damper valve or duct
bend (L > 3 x duct Ø).
Operating
speed cannot
be reached.
Faulty motor winding.
Winding measure-
ment.
Replace electric motor
_
Improper phase volt-
age.
Measure phase volt-
age.
Check/replace fuses,
motor connection ca-
ble, FC cable.
Motor overload due to
improperly positioned
damper valve.
Measure flow rate and
pressure at the operat-
ing point.
Set damper valve to
proper position.
Motor overload due to
system changes.
Fan/electric motor no
longer meeting the op-
erating point.
Consult with point of
contact (see title
page).
FC error mes-
sage.
Improper setting of
motor characteristics,
start/stop ramps, ac-
celeration/braking
time.
FC display: check rele-
vant parameters.
Set parameters prop-
erly
_
FC error mes-
sage. No ac-
celeration from
low frequency.
FC current limits are
exceeded due to insuf-
ficient power factor
(cos φ).
FC current limits too
low?
Adjust FC parameter
"Motor characteris-
tic" (torque quadratic
to speed)
_
47].
Improper motor and/or
FC size.
Motor and/or FC too
small?
Design FC according
to motor
_
47].
Start ramp too steep
or acceleration time
too short.
Check FC parameters. Adjust start ramp. In-
crease acceleration
time.
Motor protec-
tion switch,
PTC thermistor
tripping device,
or FC switches
off.
Improper setting.
Measure current draw. Set motor protection
switch properly
_
Check FC parameters. Parameterize FC prop-
erly.
Faulty motor connec-
tion.
Measure current draw. Check motor connec-
tion (star/delta)
_
52].