Manual / Manuel 

 
Central de detección y alarma de incendios convencional 

Conventional fire detection and fire alarm control panel 

Central de détection et alarme d’incendie conventionelle 
 

CLVR02Z / CLVR04Z / CLVR08Z / CLVR12Z 

Summary of Contents for CLVR02Z

Page 1: ...Manuel Central de detección y alarma de incendios convencional Conventional fire detection and fire alarm control panel Central de détection et alarme d incendie conventionelle CLVR02Z CLVR04Z CLVR08Z CLVR12Z ...

Page 2: ...3 Descripción Instalación de la central 8 4 Regletas de conexión 10 5 Funcionamiento de la central 12 5 1 Descripción 12 5 2 Esquemas de conexión 13 6 Niveles de acceso a la central 14 7 Configuración de la central 15 7 1 Configuración de retardos 15 7 2 Desconexión de zonas 16 7 3 Configuraciones alternativas por microswitch 17 8 Funcionalidades adicionales 19 8 1 Modbus 19 8 2 Contactid 19 9 Pru...

Page 3: ...ción externa para electroimanes de puertas cortafuegos sirenas módulos de relés etc modelos CLVR02Z y CLVR04Z tienen 1 salida Dispone de Modo de pruebas para facilitar la comprobación de detectores y pulsadores de forma rápida y sencilla Permite configurar los umbrales de línea abierta alarma detector y alarma pulsador para ajustarse al funcionamiento con otros detectores Admite configurar la últi...

Page 4: ... Teclas de Mando A continuación se describe el significado de las indicaciones luminosas y las teclas de mando del panel de control de las centrales CLVR02Z CLVR04Z CLVR08Z y CLVR12Z Dicho panel de control de estas centrales es común para todas ellas variando únicamente en el número de LEDs de indicación de zonas 2 1 1 Indicadores luminosos Figura 1 Panel de control de la central valido para CLVR0...

Page 5: ... de baterías Ámbar Avería de CPU Fijo Central no operativa Ámbar Comunicación de la Central a través del puerto RS485 Intermitente Central comunicando Ámbar Nivel de acceso al teclado del panel de control de la central Apagado Nivel 1 Fijo Nivel 2 Intermitente Nivel 3 Ámbar Paro sirenas Fijo Relé de sirena general en posición silencio Ámbar Anulación de retados de la central Fijo Central funcionan...

Page 6: ...12Z FABRICANTE DE PRODUCTOS CONTRA INCENDIOS Ctra de Molins de Rei a Rubí Km 8 4 08191 RUBÍ Barcelona ESPAÑA Tlf 34 935 862 690 Fax 34 936 999 261 cofem cofem com www cofem com 6 2 1 2 Teclas de mando Figura 2 Panel de control de las centrales CLVR02Z CLVR04Z CLVR08Z y CLVR12Z ...

Page 7: ...dean los leds de relés Sirena y Avería Siguientes pulsaciones Cambia el relé seleccionado parpadea solo ese led Desactivación de la señal acústica de la central zumbador por alarma o avería Accesible desde nivel de acceso 1 1 pulsación apaga el sonido del zumbador En caso de nueva incidencia el zumbador se activa automáticamente Bloqueo desbloqueo de la sirena general Accesible desde nivel de acce...

Page 8: ...ón de la central La central CLVR se basa en un cofre metálico en cuyo interior se sitúan los diferentes componentes La puerta se fija en el cofre mediante 4 tornillos frontales letra A en la figura 3 situados cerca de las esquinas Figura 3 Diagrama cofre y puerta central Figura 4 Dimensiones puerta y cofre central mm A Orificio de fijación Puerta Central B Pretaladro para acceso de cableado C Orif...

Page 9: ... acceso del cableado a la central Letra B en la figura 3 Para la instalación del cofre a la pared existen 4 orificios de diámetro 8 mm distribuidos en la cara posterior cerca de las esquinas letra C de la figura 3 Por tanto el proceso de instalación de la central es el siguiente ver figura 3 Realizar los taladros necesarios para sujetar la central en la pared Para ello tener en cuenta los orificio...

Page 10: ...prendida entre 8 y 15 5 Vdc Por su parte en Alarma pulsador lo hace entre 3 y 8 Vdc Por debajo de 3 Vdc aprox se indica línea cruzada Los umbrales de línea abierta alarma detector y alarma pulsador pueden ser variados usando los microswitch situados en la CPU ver capítulo 7 3 NOTAS La central CLVR08Z contiene conectores solo hasta 8 zonas Figura 5 2 Salidas de Sirena La central dispone de 2 salida...

Page 11: ... Permite la conexión de las baterías a la central A través de esta conexión se realiza la carga de las baterías así como la monitorización de su estado Esta salida está protegida contra la inversión de polaridad La capacidad de las baterías que se incorporen a la central dependerán del número de zonas y cargas adicionales p ej Sirenas electroimanes de puertas cortafuego etc Se recomienda usar bate...

Page 12: ...bién inmediatamente Las salidas de sirena general están supervisadas Para alimentar elementos externos al sistema de detección y alarma de incendios pero ligados a él como por ejemplo los electroimanes de puertas cortafuegos paneles luminosos etc se pueden usar Fuentes de Alimentación Externa FAE o la salida de 30V de la central dependiendo del consumo de acuerdo a los esquemas de conexión de este...

Page 13: ... CLVR08Z CLVR12Z FABRICANTE DE PRODUCTOS CONTRA INCENDIOS Ctra de Molins de Rei a Rubí Km 8 4 08191 RUBÍ Barcelona ESPAÑA Tlf 34 935 862 690 Fax 34 936 999 261 cofem cofem com www cofem com 13 5 2 Esquemas de conexión Figura 6 Ejemplo de conexión para central CLVR ...

Page 14: ... el nivel de acceso 2 NOTA El número que aparece en la tecla de mando corresponde a su descripción en el capítulo 2 1 2 y NO el número de veces que se debe pulsar Figura 7 Teclas utilizadas en los niveles de acceso de centrales CLVR02Z 04Z 08Z 12Z Nivel de acceso Combinación de Teclas orden de pulsación Funcionalidad 1 Ninguna Paro zumbador 2 Acciones de Nivel 1 Paro Sirenas Sin retardo Desconexió...

Page 15: ...ivar el nivel de acceso 2 pulsar 1 vez en el siguiente orden las teclas de mando Selección Zona Reset Autotest Selección Zona Reset Autotest 2 Activar el nivel de acceso 3 pulsar 1 vez en el siguiente orden las teclas de mando Modo pruebas Desconexión Modo pruebas Desconexión 3 Seleccionar el relé al que se le quiere aplicar el retardo mediante la tecla de mando de Selección relé 4 Pulsar la tecla...

Page 16: ...ún evento Para desconectar una zona o volverla a conectar el procedimiento es el siguiente 1 Activar el nivel de acceso 2 pulsar 1 vez en el siguiente orden las teclas de mando Selección Zona Reset Autotest Selección Zona Reset Autotest 2 Seleccionar la zona a la que se le quiere aplicar la desconexión mediante la tecla de mando de Selección Zona 3 Pulsar la tecla de mando Desconexión Nota La cone...

Page 17: ... numerados 1 y 2 permiten cambiar el umbral de línea abierta CONFIGURACION uSwitch DESCRIPCIÓN El umbral de línea abierta se sitúa en 22 6 V Configuración por defecto de la central El umbral de línea abierta se sitúa en 20 6 V El umbral de línea abierta se sitúa en 21 6 V El umbral de línea abierta se sitúa en 19 6 V 7 3 2 Configuración del umbral de alarma detector en el microswitch Los interrupt...

Page 18: ... de trabajo de la Última Zona de la central Ejemplo Zona 8 de la Central CLVR08Z Esta Última Zona puede funcionar como una zona normal de detección o bien ser usada como supervisión de un sistema externo de protección contra incendios En este caso usando una resistencia en serie de 470 Ω se produce una indicación de avería de línea abierta en esta Última Zona de la central en vez de alarma ver eje...

Page 19: ...ma que se comunica con la central CLVR se deben solicitar a su vendedor Figura 13 Comunicación MODBUS Aprovechando este sistema de comunicación se puede implementar un sistema ON LINE de la central CLVR en un PC ver ejemplo en la figura 12 opción 1 Esta opción necesita Conversores de RS485 al necesario para comunicarse con un PC normalmente RS232 o ethernet Instalar un software en el PC este softw...

Page 20: ...á 24 27 Vdc 4 ZONAS Con el sistema en reposo la tensión en los bornes de salida de las zonas será de 22 Vdc 5 SIRENA En la regleta de conexión debe haber 14 Vdc No debe estar desconectada La central deberá situarse en modo de reposo activándose únicamente el indicador luminoso de red B ver capítulo 2 1 1 Una vez realizadas estas comprobaciones se procederá con la configuración de la central y o el...

Page 21: ...cto Común Normalmente Abierto NO pasa a estar cortocircuitado y se activa el led del Relé de avería G transcurrido el tiempo de retardo configurado 3 Rearmar la central Deben desactivarse todos los indicadores luminosos a excepción del B de red ver capítulo 2 1 1 4 Comprobar que el contacto Común Normal Abierto NO no está cortocircuitado 5 Repetir las operaciones de los pasos 2 a 4 con todas las z...

Page 22: ...activa el led del Relé de avería G transcurrido el tiempo de retardo configurado 2 Comprobar que las baterías tienen una tensión de 27 1 Vdc 3 Conectar las baterías y verificar que los indicadores anteriores se desactivan en un tiempo máximo de 10 segundos además de que el contacto Común Normal Abierto NO de la salida de avería no está cortocircuitado 4 Desconectar la entrada de red a la central y...

Page 23: ... alarma En este modo de pruebas todos los relés de la central están desconectados por lo que no se enviará ningún tipo de señal fuera de la central Nota Si persiste la alarma del detector o pulsador transcurrido el tiempo de reseteo automático la central entrará en modo de avería activándose el zumbador y los indicadores luminosos D y G Para acceder o salir de este Modo de Pruebas se debe actuar d...

Page 24: ...etir las operaciones de la 1 a la 5 para todas las zonas que se necesiten 10 Consulta de la versión de software y versión de configuración de retardos de la central La central CLVR permite consultar tanto la versión de software de la CPU como la versión de configuración de retardos La versión de software de la CPU es un dato introducido en fábrica Por su parte la versión de configuración de retado...

Page 25: ...dores utilizados en las consultas de versión de software y versión de configuración de retardos 11 Puesta en marcha y Mantenimiento de la central Para la puesta en marcha y mantenimiento de la central se deberán realizar todas las pruebas de la central y el sistema que se detallan en este manual ver capítulo 8 teniendo siempre en cuenta lo que determine la legislación vigente o la autoridad compet...

Page 26: ... of the control panel 32 4 Connecting blocks 34 5 Operation of the control panel 36 5 1 Description 36 5 2 Wiring diagrams 37 6 Access levels to the contro panel 38 7 Configuration of the control panel 39 7 1 Configuration of delays 39 7 2 Disabling of zones and delays 40 7 3 Microswitch alternative settings 41 8 Aditional functions 43 8 1 Modbus 43 8 2 Contactid 43 9 Operational tests 44 9 1 Cont...

Page 27: ...acts Two 30V DC monitored auxiliary outputs protected by a fuse for external power supply as sounders relay units etc CLVR02Z and CLVR04Z models have 1 output It has a test mode for quickly and easy checking of detectors and manual call points It allows configuration of the Open line alarm detector and alarm manual call point thresholds for adjusting to operation with other detectors The last dete...

Page 28: ...m cofem com www cofem com 28 2 Control Panel 2 1 Indication leds and control keys Described below is the meaning of the indication leds and control keys of the main fire control panel CLVR02Z CLVR04Z CLVR08Z CLVR12Z This lay out is the same for all models The only difference is the number of zone leds 2 1 1 Indication leds Figure 1 Main CLVR02Z CLVR04 CLVR08 CLVR12 zones Control Panel Indicator le...

Page 29: ...el not operating Amber Control Panel communication through RS485 port Intermittent Control panel communicating Amber Level of access to keyboard of Control Panel Off Level 1 Fixed Level 2 Intermittent Level 3 Amber Silence sounders Fixed General relay sounder in silent position Amber Disable delays of panel Fixed Control panel operating without delays at the general sounder outputs fault and extin...

Page 30: ...VR04Z CLVR08Z CLVR12Z FIRE PROTECTION MANUFACTURER Ctra de Molins de Rei a Rubí Km 8 4 08191 RUBÍ Barcelona ESPAÑA Tlf 34 935 862 690 Fax 34 936 999 261 cofem cofem com www cofem com 30 2 1 2 Control keys Figure 2 Main CLVR02Z CLVR04Z CLVR08Z CLVR12Z zones Control Panel ...

Page 31: ...All relay LEDs will flash Sounder Fault Subsequent pressings Changes the selected relay only that LED will flash Deactivation of the acoustic signal of the control panel due to alarm or fault Accessible from access level 1 1 pressing switches off the sounder noise In the event of a new incident the buzzer will activate automatically Locking unlocking of the general sounder Accessible from access l...

Page 32: ... Description Installation of the control panel The control panel CLVR is based on a metal box into which the different components are placed The door is fitted to the box with 4 front bolts letter A in figure 3 located near the corners Figure 3 Diagram of box and main door Figure 4 Door and main box measurements mm A Fastering hole Main Door B Pre drilled hole for wiring access C Fastering hole Co...

Page 33: ... of 8 mm diameter on the rear side near the corners letter C in figure 3 Therefore the installation process for the control panel is as follows see figure 3 Drill the necessary holes for mounting the control panel on the wall To do this remember holes C located in the corners of the cover see figure 3 Remove the box door by taking out bolts A from the corners Open the pre drilled holes B needed fo...

Page 34: ...all point thresholds can be modified using the CPU microswitches see chapter 7 3 NOTES CLVR08Z has connectors only up to 8 zones Figure 5 2 Sounder output Control Panel has 2 sounder outputs monitored and independent with simultaneous activation protected by a fuse In this way in case of fault in one output the other can still be operated by the control panel The outputs are activated simultaneous...

Page 35: ...t reverse polarity The capacity of the batteries connected to the control panel will depend on the number of zones and additional charges e g Sounders door electromagnets and fire doors etc The use of 7 Ah batteries is recommended 7 Fuses CLVR02Z CLVR04Z CLVR08Z y CLVR12Z Control Panel Batteries fuse FUS2 FUS31 4 A Fuse 30V Autoresettable Fuse 0 75 A 1 5 A1 Fuse S1 Autoresettable Fuse 1 A 1 85 A1 ...

Page 36: ... been programmed If this is not the case it will also be activated and indicated immediately The general sounder output is monitored In order to supply components outside of but connected to the detection and fire alarm system such as the electromagnets of the fire doors lighting panels etc External Power Sources EPS can be used or the 30V output of the control panel depending on the consumption i...

Page 37: ...s de Rei a Rubí Km 8 4 08191 RUBÍ Barcelona ESPAÑA Tlf 34 935 862 690 Fax 34 936 999 261 cofem cofem com www cofem com 37 5 2 Wiring diagrams Figure 6 Example of general wiring diagram NOTE1 This card has 4 or 8 Zones depending on the model CLVR08Z CLVR12Z NOTE2 Last zone configured for monitoring an external fire protection system ...

Page 38: ...first activate level 2 NOTE The number appearing on the control key corresponds to its description in chapter 2 1 2 and NOT to the number of times it must be pressed Figure 7 Keys used in the control panel access levels CLVR02Z 04Z 08Z 12Z Access level Key combination order of pressing Functionality 1 None Stop buzzer 2 Level 1 actions Stop sounders No delay Disable zones relays Zone test mode 3 L...

Page 39: ...rocedure is as follows 1 Activate access level 2 press the control keys once in the following order Zone Relay selection Reset Autotest Zone Relay selection Reset Autotest 2 Activate access level 3 press the control keys once in the following order Test mode Disable Test mode Disable 3 Select the relay to which you wish to apply the delay using the control key Select Relay 4 Press the control key ...

Page 40: ...will be cut on the disabled zones and no event will be generated on them In order to disable or re enable a zone the procedure is as follows 4 Activate access level 2 press the control keys once in the following order Zone Selection Reset Autotest Zone Selection Reset Autotest 5 Select the zone which is to be disabled using the control key Select Zone 6 Press the General Disable control key Note E...

Page 41: ...ing at the uSwitch The switch with numbers 1 and 2 allow modification of the open line threshold uSwitch CONFIGURATION DESCRIPTION Open line threshold at 22 6 V Default Control panel setting Open line threshold at 20 6 V Open line threshold at 21 6 V Open line threshold at 19 6 V 7 3 2 Detector Alarm thershold setting at the uSwitch The switch with numbers 3 and 4 allow modification of the Detecto...

Page 42: ...tion of the Last Zone of the Control Panel example zone 8 of the CLVR08Z This Last Zone can work as a normal detection zone or for the monitoring of a fire warning external device In this last case using a serial resistance of 470 Ω with the fire warning external device gives indication of Open line fault at the Last Zone of the Control panel instead of an alarm see example in the wiring diagram o...

Page 43: ...ected with CLVR control panel must be requested to seller Figura 13 MODBUS Communication Taking advantage of this communication system it can be implemente dan ON LINE CLVR system in a PC see example of figure 12 option 1 This option requires RS485 conversor to the PC port protocol normally RS232 or ethernet Installation of a software in a PC by default this software contents the required MODBUS t...

Page 44: ...e 24 27 Vdc on the battery terminals 4 ZONES With the system in standby the voltage on the zone output terminals will be 22 Vdc 5 SOUNDER On the terminal box there must be 14 Vdc It must not be disconnected The control panel must be put into standby mode by pressing only the B indication led see chapter 2 1 1 Once these checks have been carried out proceed with the configuration of the control pan...

Page 45: ... fault respectively b Common Normally Open NO Fault contacts are shorted and the fault relay indicator led G illuminates once the configured delay time is passed 3 Resetting control panel All the indicator leds must be disabled with the exception of B power supply see chapter 2 1 1 4 Check that Common Normally Open NO Fault contacts are electrically open 5 Repeat operations 2 to 4 with all active ...

Page 46: ...ault contacts are shorted and the fault relay G is activated after the configured time delay 2 Check that the batteries have a voltage of 27 1 Vdc 3 Connect the batteries and check that the previous indicators are disabled in a maximum time of 10 seconds and Common Normally Open NO Fault contacts are electrically open 4 Disconnect the power supply input to the control panel and check that a The po...

Page 47: ...after the alarm triggers In this test mode all the control panel relays are disabled therefore no signal of any kind will be sent outside the control panel Note If the detector or call point alarm persists after the automatic reset time the control panel will enter in fault mode activating the buzzer and the leds D and G In order to gain access to or exit from this Test Mode the following must be ...

Page 48: ...s 1 to 5 for all the zones that may need it 10 Reference of software version and configuration version of delays in the control panel The CLVR control panel has references for the CPU software version as well as the delay configuration version The CPU software version is inserted by the manufacturer For its part the delay configuration version counts the number of times that the delays are configu...

Page 49: ...cofem com 49 Figure 17 Keys and indicators used to reference the version of software and the delay configuration software version 11 Start up and Maintenance of the Control panel All the test listed in this manual see chapter 9 must be carried out in order to start up and maintain the control panel always keeping in mind the current legislation or competent authority in each case 12 Additional inf...

Page 50: ...lettes de connexion 58 5 Fonctionnement de la centrale 60 5 1 Description 60 5 2 Schémas de connexion 61 6 Niveaux d accès à la centrale 62 7 Configuration de la centrale 63 7 1 Configuration des retards 63 7 2 Déconnexion de zones et relais 64 7 3 Configurations alternatives par microcommutateur 65 8 Fonctionnalités additionnelles 67 8 1 Modbus 67 8 2 Contactid 67 9 Essais de fonctionnement 68 9 ...

Page 51: ...visées et protégées par un fusible pour alimentation externe pour sirènes modules de relais etc modèles CLVR02Z et CLVR04Z ont une sortie Dispose de Mode d essais pour faciliter la vérification de détecteurs et déclencheurs de façon rapide et simple Permet definir seuils de ligne ouverte alarme de détecteur et button d alarme pour ajuster avec d autres détecteurs Prise en charge de definir la dern...

Page 52: ...ants lumineux et Touche de Commande La signification des voyants lumineux et des touches de commande du panneau de contrôle de les centrales CLVR02Z CLVR 04Z CLVR 08Z et CLVR 12Z est indiquée ci dessous Ce panneau de contrôle de ces centrales est commun pour toutes en variant uniquement dans le numéro de LEDs d indication de zones 2 1 1 Voyants lumineux Figure 1 Panneau de contrôle de les centrale...

Page 53: ...chargées ou absence Clignotant Panne du chargeur de batteries Orange Panne de CPU Fixe Centrale non opérationnelle Orange Communication de la centrale à travers le port RS485 Clignotant Centrale communiquer Orange Niveau d accès au clavier du panneau de contrôle de la centrale Éteint Niveau 1 Fixe Niveau 2 Clignotant Niveau 3 Orange Arrêt sirènes Fixe Relais de sirène général en position silence O...

Page 54: ...R12Z FABRICANTS DE PRODUITS CONTRE INCENDIES Ctra de Molins de Rei a Rubí Km 8 4 08191 RUBÍ Barcelona ESPAÑA Tlf 34 935 862 690 Fax 34 936 999 261 cofem cofem com www cofem com 54 2 1 2 Touches de commande Figure 2 Panneau de contrôle de les centrales CLVR02Z CLVR04Z CLVR08Z et CLVR12Z ...

Page 55: ...uis niveau d accès 2 1 pulsation Clignotent les leds de relais Sirène et Avarie Pulsations suivantes Il change le relais choisi clignote seulement celui là led Désactivation du signal acoustique de la centrale par alarme ou panne Accessible depuis niveau d accès 1 1 pulsation éteint le bruit du sonnerie En cas de nouvel incident la sonnerie s activera automatiquement Blocage déblocage de la sirène...

Page 56: ...ation de la centrale La centrale CLVR est composée d un coffre métallique à l intérieur duquel se trouvent différents composants La porte se fixe sur le coffre au moyen de 4 vis frontaux lettre A sur la figure 3 situées près des coins Figure 3 Diagramme coffre et porte centrale Figure 4 Dimensions porte et coffre centrale mm A Orifice de fixation Porte Centrale B Trou pré percé pour accès de câbla...

Page 57: ...lation du coffre sur le mur il y a 4 trous d un diamètre de 8 mm distribués sur le panneau arrière près des coins lettre C de la figure 3 Par conséquent le processus d installation de la centrale est le suivant voir figure 4 Réaliser les trous nécessaires pour fixer la centrale au mur Pour cela tenir compte des orifices C dans les coins du coffre voir figure 3 Démonter la porte du coffre en retira...

Page 58: ...étecteur et alarme déclencheur ils peuvent être variés en utilisant le microcommutateur situés dans la CPU voir un chapitre 7 3 REMARQUE La centrale CVLR 08Z contient des connecteurs seulement jusqu à 8 zones Figure 5 2 Sortie de Sirène La centrale dispose de 2 sorties de sirène supervisées indépendantes d un démarrage simultané protégées par un fusible De la sorte dans le cas d avarie dans une so...

Page 59: ...oring de son état Cette sortie est protégée contre l inversion de polarité La capacité des batteries connectées à la centrale dépendra du nombre de zones et charges supplémentaires p ex Sirènes électroaimants de porte coupe feu etc Il est recommandé d utiliser des batteries de 7Ah 7 Fusibles Centrales CLVR02Z CLVR04Z CLVR08Z et CLVR12Z Fusibles Batteries FUS2 FUS31 4 A Fusible 30V Fusible autorear...

Page 60: ... indiquée aussi immédiatement La sortie de sirène générale est supervisée Pour alimenter des éléments externes au système de détection et alarme d incendies mais reliés à celui ci comme par exemple des électro aimants de porte coupe feu des panneaux lumineux etc on peut utiliser des Sources d Alimentation Externe SAE ou la sortie de 30 V de la centrale selon la consommation conformément aux schéma...

Page 61: ...e Rei a Rubí Km 8 4 08191 RUBÍ Barcelona ESPAÑA Tlf 34 935 862 690 Fax 34 936 999 261 cofem cofem com www cofem com 61 5 2 Schémas de connexion Figure 6 Exemple de connexion pour centrale CLVR NOTE 1 Cette carte contient 4 ou 8 zones en dépendant du modèle CLVR08Z CLVR12Z NOTE 2 Il finalise une zone configurée pour supervision de système externe ...

Page 62: ...ès 2 REMARQUE Le numéro figurant sur la touche de commande correspond à sa description au chapitre 2 1 2 et NON PAS au nombre de fois qu il faut appuyer Figure 7 Touches utilisées dans les niveaux d accès centrales CLVR02Z 04Z 08Z 12Z Niveau d accès Combinaison de Touches ordre de pulsation Fonctionnalité 1 Aucune Arrêt sonnerie 2 Actions de Niveau 1 Arrêt sirènes Sans retard Déconnexion zones Mod...

Page 63: ...re est la suivante 1 Activer le niveau d accès 2 appuyer 1 fois dans l ordre suivant sur les touches de commande Sélection Zone Reset Autotest Sélection Zone Reset Autotest 2 Activer le niveau d accès 3 appuyer 1 fois dans l ordre suivant sur les touches de commande Mode essai Déconnection Mode essais Déconnection 3 Sélectionner le relais auquel on veut appliquer le retard au moyen de la touche de...

Page 64: ...énement particulier Pour déconnecter ou reconnecter une zone la procédure est la suivante 1 Activer le niveau d accès 2 appuyer 1 fois dans l ordre suivant sur les touches de commande Sélection Zone Reset Autotest Sélection Zone Reset Autotest 2 Sélectionner la zone à laquelle on veut appliquer la déconnexion au moyen de la touche de commande Sélectionner zone 3 Appuyer sur la touche de commande D...

Page 65: ...dénombrés 1 et 2 permettent de changer le seuil de ligne ouverte CONFIGURACION MICROCOMMUT DESCRIPTION Le seuil de ligne ouverte se situe dans 22 6 V Configuration par défaut de la centrale Le seuil de ligne ouverte se situe dans 20 6 V Le seuil de ligne ouverte se situe dans 21 6 V Le seuil de ligne ouverte se situe dans 19 6 V 7 3 2 Configuration du seuil de alarme détecteur sur le microcommutat...

Page 66: ... de la centrale l Exemple la Zone 8 de la Centrale CLVR08Z Cette dernière Zone peut fonctionner comme une zone normale de détection ou bien être utilisée comme supervision d un système externe de protection contre des incendies Dans ce cas en utilisant une résistance dans une série de 470 Ω se produit une indication d avarie de ligne ouverte sur cette dernière Zone de la centrale au lieu de l alar...

Page 67: ...i communique avec la centrale CLVR doivent être demandées à son vendeur Figura 13 Communication MODBUS En mettant ce système de communication à profit on peut mettre en application un système EN LIGNE de la centrale CLVR dans un PC voir un exemple dans la forme 12 une option 1 Cette option a besoin les Convertisseurs de RS485 au nécessaire pour communiquer avec un PC normalement RS232 ou un ethern...

Page 68: ...erie 4 ZONES Avec le système au repos la tension dans les bornes de sortie des zones sera de 22 V 5 SIRÈNE Dans la réglette de connexion il devra y avoir 14 Vdc elle ne doit pas être déconnectée La centrale devra être en mode de repos seul le voyant lumineux de réseau B devra être activé voir chapitre 2 1 1 Après avoir réalisé ces vérifications procéder à la configuration de la centrale et ou aux ...

Page 69: ...ent b Le contact Commun Normalement Ouvert NO il se met à être court circuité et s active le led du Relais d avarie G écoulé le temps de retard configuré 3 Réarmer la centrale Tous les voyants lumineux doivent se désactiver sauf le B de réseau voir chapitre 2 1 1 4 Vérifier que le contact Commun Normalement Ouvert NO n est pas court circuité 5 Recommencer les opérations 2 à 4 avec toutes les zones...

Page 70: ...active le led du Relais d avarie G écoulé le temps de retard configuré 2 Vérifier que les batteries ont une tension de 27 1 Vdc 3 Connecter les batteries et vérifier que les indicateurs antérieurs sont désactivés dans le temps maximal de 10 seconds en plus duquel le contact Commun Normalement Ouvert NO n est pas court circuité 4 Débrancher l entrée du secteur à la centrale et vérifier a Le voyant ...

Page 71: ...chement de l alarme Dans ce mode d essais tous les relais de la centrale sont déconnectés donc aucun signal ne sera envoyé hors de la centrale Remarque Si l alarme du détecteur ou du bouton persiste après le temps du reset automatique la centrale entrera en mode de panne et activera la sonnerie et les voyants lumineux D et G Pour accéder ou sortir de ce Mode d Essais agir de la façon suivante 1 Ac...

Page 72: ...ns 1 à 5 pour toutes les zones nécessaires 10 Consultation de la version de software et version de configuration de retards de la centrale La centrale CLVR permet de consulter autant la version de software du CPU que la version de configuration des retards La version de software du CPU est une donnée introduite en usine Pour sa part la version de configuration de retards comptabilise le nombre de ...

Page 73: ...m com www cofem com 73 Figure 17 Touches et voyants utilisés dans les consultations de version de software et version de configuration de retards 11 Mise en marche et Maintenance de la Centrale Pour la mise en marche et la maintenance de la centrale réaliser tous les essais de la centrale et du système détaillés dans ce manuel voir chapitre 9 en tenant toujours compte de la législation en vigueur ...

Page 74: ...DIOS FIRE PROTECTION MANUFACTURER FABRICANTSDE PRODUITS CONTRE INCENDIES Ctra de Molins de Rei a Rubí Km 8 4 08191 RUBÍ Barcelona ESPAÑA Tlf 34 935 862 690 Fax 34 936 999 261 cofem cofem com www cofem com 74 12 Información adicional Aditional Information Information additionnelle 12 1 Figura 18 Figure 18 ...

Page 75: ...nal Operational reliability Cumple Passed Duración de la seguridad operacional y retardo a la respuesta resistencia a la temperatura Durability of operational reliability Temperature resistance Cumple Passed Duración de la seguridad operacional y retardo a la respuesta resistencia a la vibración Durability of operational reliability Vibration resistance Cumple Passed Duración de la seguridad opera...

Page 76: ... com sat1 cofem com ventas1 cofem com ventas2 cofem com cofem cofem com Atención Técnico Comercial Ventas 34 902 448 811 34 935 862 690 C S Sales 34 935 862 694 34 902 338 811 sat2 cofem com tecnic cofem com compras cofem com export cofem com Export Fax pedidos S A T Compras 34 935 862 692 34 935 862 693 Technical Commercial Service T A S Purchase Export 34 902 338 811 34 936 999 261 Fax pedidos F...