LANGUAGE
ENGLISH
MAX. INT. PUMP 1
OFF
MAX. INT. PUMP 2
OFF
MIN. SPEED
30 Hz
LEVEL PROBE
NO
P LINE SET P
0,0 bar 0,0 bar
PROGRAMMING MENU
SET PRESSURE
2,0 bar
DIF. START
0,3 bar
VIEW MODE
PRESSURE
P LINE SET P.
0,0 bar 0,0 bar
Hz LINE SET P.
42 2,0 bar 2,0
ENTER
ENTER
AUTOMATIC
CONFIGURATION.
By mean of
p
q
we can change the values and press ENTER for validation. Whenever we want to quit the
configuration sequence press MENU. After every ENTER it will appear automatically the different screens that
constitute the sequence of configuration.
0. To start configuration sequence push MENU during 3”.
1.By mean of keys
p
q
we can choose the languages: “LANGUAGE ENGLISH”,
“LANGUE FRANÇAISE”, “LINGUA ITALIANA” e “IDIOMA ESPAÑOL”.
2. By mean of keys
p
q
enter the nominal intensity value in A of pump 1 enabling
the thermal protection. This value is located over the characteristics plate of the
motor. Press ENTER for validation.
3. Follow instructions of the previous step. See intensity value in A over the
characteristics plate.
4. Using
p
we can increase the lower limit of the speed of rotation of the main
pump´s motor.The default value is 30 Herz .
5. If the installation does not have level probe press ENTER to validate NOT. If
the installation has a level probe, by mean of keys
p
q
we can change NO by
YES.
6. Being inside configuration menu we are having access to the phase of
programming.
7. This will be the system working pressure. Use keys
p
q
for modify the initial
value (2 bar). WARNING ! SET pressure must be under 12 bar.
8.The default value is 0,3 bar. This value of pressure is the one that the system
will subtract to the input pressure, resulting the final pressure to which the
system will SET ALT in motion when the hydraulic network have a demand.
Using keys
p
q
to modify the initial value. It is recommended to maintain this
value between 0,3 and 0,6 bar. Example:
- Input pressure:
2 bar.
- Differential start:
0,3 bar.
- Final start pressure:
2 - 0,3 = 1,7 bar.
The value should be greater as much as smaller be the accumulation and vice
versa.
9. There are 2 view modes to choose::
- Pressure: it is visualized “P LINE” (real pressure of the installation) and “SET P”
(working programmed pressure).
- Service: it is visualized “Hz” (working frequency of the inverter), “LINE” (input
pressure chosen), “SET P” (real pressure of the installation)
10. After pressing ENTER pushbutton, the system will remain configured showing
the type of view chosen in the previous section.
Press AUTOMATIC in order to quit manual mode.