background image

5

LEDS

DISPLAY

ACTION

bar/psi

O

Is displayed on screen the instan-

taneous pressure in bar or psi

( ( O ) )

Pump ON and is displayed on 

screen the instantaneous pressure 

in bar or psi

A

(only 

DGplus 

and 

DGM2)

O

Is displayed on screen the instan-

taneous current consumption in 

Ampere units

( ( O ) )

Pump ON and is displayed on 

screen the instantaneous current 

consumption in Ampere units

P START

O

Is displayed the start pressure

( ( O ) )

Adjusting start pressure

P  STOP

O

Is displayed the stop pressure

(only in pressure dependent 

MODE)

( ( O ) )

Adjusting stop pressure 

(only in pressure dependent 

MODE)

FLOW

O

It indicates positive flow

ALARM

O

Ratified dry-running or overload 

alarms

( ( O ) )

Dry-running alarm performing ART 

or overload alarm preforming any 

of the 4 restore attempts

P-BUT

TON

TOUCH

ACTION

click!

From state ON

: any alarm is res-

tored.

From state OFF

: system changes to 

STATE ON, the pump starts.

From any configuration MENU

the parameter value is accepted.

HOLD 

DOWN

From state ON

: unit OFF, relay 

disconnection.

From state OFF

: the pump starts 

and keeps operating until the 

push-button is released.

click! Pstop is displayed on the screen for 

3 seconds.

click!

Inside CONFIG or ADJUSTMENT 

modes is used to increase the para-

meters values.

3”

Pstop adjustment mode.

click! Pstart is displayed on the screen for 

3 seconds.

click!

Inside CONFIG or ADJUSTMENT 

modes is used to dicrease the para-

meters values.

3”

Pstart adjustment mode.

(only DG-

plus and 

DGM2)

click!

Is displayed on the screen instanta-

neous current consumption. 

If it is already displayed then we 

switch to instantaneous pressure 

view.

3”

Rated current adjustment.

STARTUP (diagram C)

 

Before starting the device please read the pre-

vious sections, especially “Hydraulic Installation” 

and “Electrical connection”.

Follow next steps:

1. Start the device by pressing  .

2. 

(only DGplus and DGM2) 

    Set the pump rated current intensity value:

-  Press    during 3 seconds.

- The current intensity value is displayed on screen 

and LED A is flashing (factory setting 16A). 

- By mean of   and   is adjusted the rated cu-

rrent reflected in the characteristics plate of the 

motor. See Note 1.

- Press   for validation.

3. Set the cut-in (start) pressure:

- Press     during 3 seconds.

- The start pressure value is displayed on screen 

and LED START is flashing. 

- By mean of   and   is adjusted the start pressu-

re from 0,5 to 7 bar.

 *If it is higher than 3 bar, it 

is advisable to use a small expansion tank.

- Press   for validation.

4. Set the cut-out pressure (only if it has been set on 

ADVANCED MENU the pressure dependent operation 

mode):

- Press     during 3 seconds.

- The stop pressure value is displayed on screen 

and LED STOP is flashing. 

- By mean of   and   is adjusted the stop pressu-

re from 1 to 8 bar.

 

- Press   for validation.

In pressure dependent mode is compulsory the 

installation of a pneumatic tank.

5. The unit is ready to operate but more optional 

adjustments can be set through basic and advanced 

MENUS. See the next chapter. 

Note 1: it is important to introduce exactly the 

rated current specified on the nameplate of the 

pump. If a new pump  is installed this process 

should be repeated.

BASIC MENU 

  +   

(diagram C)

- Press simultaneously   + 

 during 5 seconds.

- By mean of   or   the values can be changed.

- Press   for validation.

- This is the parameters sequence:

TYPE

SYSTEM REACTION

FACTORY 

SETTING

bar psi We can select the pressure units 

displayed beetween bar and psi. 

bar

Summary of Contents for DIGIMATIC 1

Page 1: ...INSTRUCTIONS MANUAL MANUAL DE INSTRUCCIONES MANUALE DI ISTRUZIONI MANUEL D UTILISATION BEDIENUNGSANLEITUNG DIGIPLUS DIGIMATIC 2 DIGIMATIC 1...

Page 2: ...essione o all installazione Gefahr der Besch digung des Steuerger tes und der Druckleitungen und oder der gesamten Anlage Risk by electric shock Riesgo por choque el ctrico Risque d lectrocution Risch...

Page 3: ...If Pressure dependent mode or P start 3 bar bar psi bar psi flow flow Amps A P STOP P STOP P START P START M B N O Outlet alarms Salida alarmas Sortie alarmes Uscita alarmi Ausgang alarms DIGIPLUS A...

Page 4: ...C G 1 M Net weight without cables 1 3 kg Plugs and sockets built into the wiring of the device could modify the declared IP rating HIDRAULIC INSTALLATION diagram A Before proceeding with hydraulic con...

Page 5: ...ssure view 3 Rated current adjustment STARTUP diagram C Before starting the device please read the pre vious sections especially Hydraulic Installation and Electrical connection Follow next steps 1 St...

Page 6: ...tore the water supply After this first attempt are performed consecutive attempts every 30 minutes This function can be activated in the ADVANCED MENU It can also be set the number of attempts 1 48 an...

Page 7: ...ion can also be restored manually by pressing ENTER O A04 O FAST CYCLING Hammering This alarm can be unabled or activated in the ADVANCED MENU The alarm is activated when 3 consecutive cycles occur in...

Page 8: ...8 bar Conexi n red hidr ulica DIGIPLUS G 1 1 4 M Conexi n red hidr ulica DGMATIC G 1 M Peso neto sin cables 1 3 kg Los enchufes y conectores integrados en el ca bleado del aparato podr an modificar el...

Page 9: ...aparato deber n leerse los apartados anteriores especialmente Instalaci n Hidr ulica y Conexi n el ctrica La puesta en marcha b sica consiste en 1 Poner en marcha el dispositivo pulsando 2 Configuraci...

Page 10: ...restaurar el funcionamiento normal mediante una serie de puestas en marcha peri dicas Se realiza un primer intento a los 5 mi nutos Despu s de este primer intento se realizar n intentos sucesivos cad...

Page 11: ...er restaurado manualmente pulsando ENTER O A04 O CICLOS R PIDOS S lo si la hemos activado en el MEN AVANZADO se activa la alarma cuando se producen tres ciclos consecutivos en un intervalo de tiempo e...

Page 12: ...ydr DIGIPLUS G 11 4 M Raccordement hydr DIGIMATIC G 1 M Poids net sans c bles 1 3 kg Les prises et les connecteurs int gr s dans le c blage du dispositif peuvent modifier le degr de protection IP INST...

Page 13: ...spositif en marche il faut consulter les paragraphes pr c dents notam ment Installation hydraulique et Raccordement lectrique La mise en marche de base consiste 1 Mettre en marche le dispositif en app...

Page 14: ...ed marrer la pompe afin de r tablir l alimentation d eau Apr s cette premi re tentative sont effectu es des tentati ves cons cutives toutes les 30 minutes Cette fonction peut tre activ e dans le MENU...

Page 15: ...appuyant sur ENTER O A04 O CYCLES RAPIDES Cette alarme peut tre d sactiv e ou activ e dans le MENU AVANC L alarme est activ e lorsque 3 cycles cons cutifs se produisent dans une plage inf rieure au te...

Page 16: ...TIC G 1 M Pesso netto senza cavi 1 3 kg Le spine e i connettori integrati nel cablaggio del dispositivo potrebbero modificare il grado IP INSTALLAZIONE IDRAULICA schema A Prima di procedere alla conne...

Page 17: ...ompa AVVIO schema C Prima di avviare l apparecchio dovranno essere letti i paragrafi precedenti specialmente quelli relativi a Installazione Idraulica e Connessione elettrica L avvio di base consiste...

Page 18: ...la pompa per ripristinare l alimentazione idrica Dopo questo primo tentativo vengono eseguiti tenta tivi consecutivi ogni 30 minuti Questa funzione pu essere attivata nel MENU AVAN ZATO Si pu anche i...

Page 19: ...funzionamento normale pu anche essere ripristinato manualmente premendo ENTER O A04 O CICLI ECCESSIVI Solo se l abbiamo attivato nel MENU AVANZATO si attiva l allarme quando si producono tre cicli con...

Page 20: ...des Ger ts eingebaut sind k nnen die angegebene IP Schutzart ndern HYDRAULISCHE INSTALLATION Diagramm A Vor dem Anschluss berpr fen ob die Hydraulik der Pumpe ordnungsgem installiert wurde Die sollte...

Page 21: ...n IGIMATIC 2 Einstellung der Stromst rke Dr cken Sie f r 3 Sekunden Die aktuell eingestellte Stromst rke wird auf dem Bildschirm angezeigt und die LED A blinkt Werk seinstellung 16A Mit den Tasten und...

Page 22: ...chutzes A01 oder Mindestdruck A11 gestoppt hat ver sucht der ART nach 5 Minuten die Pumpe wieder zu starten um die Wasserversorgung wiederherzustellen Nach diesem ersten Versuch erfolgt alle 30 Minute...

Page 23: ...arm kann im ERWEITERTEN MEN deaktiviert oder aktiviert werden Der Alarm wird aktiviert wenn 3 aufeinanderfolgende Zyklen in einem Bereich auftreten der niedriger ist als die eingestellte Zeit zwischen...

Page 24: ...R ENTER 3 LED A 0 37 2 2 110 230 x 1 50 60 16 0 6 IP65 50 60 7 0 5 102 7 8 1 116 14 1 5 8 G 1 1 4 M DIGIPLUS G 1 M DIGIPLUS 1 3 IP 1 A 3 110 230 H07RN F 3G1 3G1 5 U V N L DGPLUS DGM A 250 220 30 62 5...

Page 25: ...START O O P STOP O O FLOW O ALARM O O ON OFF configuration MENU ON OFF Pstop 3 CONFIG ADJUSTMENT 3 Pstart 3 CONFIG ADJUSTMENT 3 DGplus DGM2 3 1 DGM2 DGplus 2 3 16 LED A 1 3 3 LED START 3 7 0 5 4 LED S...

Page 26: ...rc0 rc1 rc2 rc2 r01 r99 rc1 rc2 3 99 r03 H00 H99 H01 H00 H24 24 H00 rs0 rs1 rs1 rs0 ART A01 ALARM 5 ART A11 30 ADVANCED MENU 1 48 10 40 APR 72 10 APr 5 REGISTER rEC HF xxx 0 65535 HP xxx 0 65535 CF x...

Page 27: ...NTER O ART 24 30 5 24 ENTER A11 O ADVANCED PROGRAMMING MENU A02 O DGM2 DGplus 4 ENTER O A04 O ADVANCED MENU 3 5 rc1 rc2 ENTER A05 O A30 O ADVANCED MENU ENTER Mbr O 200 000 200 400 600 800 Mbr ENTER O...

Page 28: ...35 UE 2014 30 UE 2011 65 UE Normes EN 60730 2 6 EN 60730 1 EN 61000 6 1 EN 61000 6 3 CEI 60730 1 CEI 60730 2 6 DICHIARAZIONE DI CONFORMIT CE Dichiariamo sotto la nostra responsabilit che i materiali d...