background image

IP65

C

B5S

 fitting

Disassembling the 

Fohn

 fitting

FOHN

/3W/M3

 

FOHN

/3W/ST

Connections for Maintained

 or

 Self-Test

 

version

3

Technical Specification:

-

Supply Voltage: 220-240V AC 50/60Hz

-

Insulation Class: II

-

Ingress Protection: IP

65

-

Emergency Duration: 3

 h

ours

-

Light Source:

 for M3 and ST version

 

3

-

Battery 6.4V 

3.

0Ah LiFEPO4 for 

3W 

M3 & ST

-

Battery Recharge Time: 12h

-

Max Battery Temperature: 55°C

-

Ambient Temperature: 0 - 40°C

-

Charge indicator: Green / Red LED

-

Deep Discharge Protection DDP

-

Self-Test version available

-

Surface assembly

-

Assembly indoors to flat surface

-

Polycarbonate body

-

Maintained or Non-Maintained Operation

Important:

It is recommended that the unit is installed by a competent person 
ensuring the installation complies with the necessary standards. The 
company accept no responsibility for incorrect installation, operation 
or maintenance. The unit requires an unswitched supply for charging 
the  battery  and  a  switched  supply  for  a  maintained  unit.  After 
installation of the fitting, the battery must be charged for 24 hours. 

LED indication Chart

Testing / Commissioning:

Ensure the load is connected
Enter  the  commissioning  date  on  battery  pack

  and 

onnect  the 

battery
Switch on the unswitched supply – Check that the green charge LED 
illuminates
Switch on the maintained supply – Check that the fitting illuminates as 
normal
Switch off the maintained supply
Switch off the unswitched supply – Check that the green charge led 
extinguishes and the fitting illuminates
Switch on the unswitched supply

It is recommended that the batteries are renewed  every 6 years.
The fitting is equipped with non-replaceable LED.

Self-Test Function:

A Function Test automatically runs every 28 days. During this test the 
fitting is switched into emergency mode for 1 minute. During the test 
the battery discharge current is checked.
A Full Duration Test automatically runs every 364 days. During this 
test the fitting is switched into emergency mode for 3 hours . During 
the test the battery discharge current and battery voltage is checked

c

4x Press to 
release

4x

!

Light source and LED indicator are connected,
be careful during opening

4x to 

release reflector

I

II

Tel. +44 (0)1376 331 515   www.cocolighting.com

www.cocolighting.com

www.cocolighting.com

Reviews: