SELF CONTAINED EMERENCY LIGHT
SERIE SIRAH LED IP65
Characteristics:
Supply 230V~ 50/60Hz.Current 80-100mA
Non Maintained.
TEST button incorporated.
Stand by and re-start via Telemando (ref: TM). (
Only for Sirah models with Telemando, supplied on demand
).
Green Led (left) indicates the battery charging & the green led (right) indicates the presence of power.
PCB 39 LED 3528, white, high luminosity, working life >50000 hours.
Color temp 6000-7000K
Diffuser in OPAL color
Grade IP65.
Connection via
16 or
20 mm cable.
Protection against the connection error of the Telemando connector. (Only for models with Telemando supplied on
demand)
Overload and end of battery discharge protection.
Class II Luminaries should be installed in a way that no metal piece exposed should in electrical contact with any part of
electrical installation connected to GROUND.
Norms Applied:
CE as per directives
2006/95/CE and 2004/108/CE of EMC
Manufactured according to norms UNE-EN 60598-2-22
Model
Emergency Lamp
E
Battery
Ni-Cd
Autonomy
luminous flux
Lumen
E-75 ECO LED
PCB 39 LED 3528 2,4W
2.4V 1.5Ah
1 hour
75
E-100 ECO LED
PCB 39 LED 3528 2,4W
2.4V 1.5Ah
1 hour
100
E-150 ECO LED
PCB 39 LED 3528 2,4W
2.4V 1.5Ah
1 hour
150
E-200 ECO LED
PCB 39 LED 3528 2,4W
2.4V 1.5Ah
1 hour
230
E-300 ECO LED
PCB 39 LED 3528 3W
4.8V 1.5Ah
1 hour
356
E-400 ECO LED
PCB 39 LED 3528 3W
4.8V 1.5Ah
1 hour
400
E-103 ECO LED
PCB 39 LED 3528 2,4W
3.6V 1.5Ah
3 hours
100
E-153 ECO LED
PCB 39 LED 3528 2,4W
3.6V 1.5Ah
3 hours
150
Installation:
Install & connect the luminary to the main supply.
Check that the yellow leds indicating the charging process & power presence are lit.
The Batteries are supplied discharged and they need 24 hours to be charged completely, so the luminary will not
respond to its autonomy until 24 hours.
Maintenance:
The Batteries should be changed once their duration gets inferior to the assigned.
The Luminaries should be checked at least once a year.
The Batteries and LED PCB should be re-cycled or eliminated in an adequate way.
Before doing any maintenance operation, please make sure that the main supply is switched off and the Luminary is
in STAND BY Position.
Verification TEST:
Verification is possible by pressing the
TEST
button on the LUMNINARY, or with the following accessory
.
TELEMANDO TM:
By pressing the button ON of TELEMANDO, the Luminary starts working on Emergency in the presence of power
(only for Sirah models which support Telemando, supplied on demand.)
*
Please note that Standard model of SIRAH is not compatible with TELEMANDO, and SIRAH TELEMANDO is
only supplied on special demand
Stand by position:
(Only for models Sirah with Telemando (supplied on demand)).
Connect the TELEMANDO TM as indicate din the Diagram of connection.
When the light is working on emergency mode it is possible to Switch OFFF the Luminary to save the Battery power
by pressing OFF on TELEMANDO.
By pressing ON the Luminary starts working again