C.M.C. n.v. - Airmaster S1 installation guide – V1.2 – MANY0402A.00
6.5 Relay outputs
The Airmaster S1 has 6 relays.
X03
R1
R2
R3
R4
R5
EXAMPLE
R6
K1
K2 K3
S1
1
4
+VC
0VC
6
1
OPTIONAL
X02
Switching Voltage (max)
240Vac / 24Vdc
Continuous Current (max)
8Aac / 8Adc (resistive load) (*)
Breaking Capacity (max)
1800VA (cosØ=1) / 150W dc
Switching Rate
300 ops/min (no load)
30 ops/min. (rated load)
Mechanical Life
10M ops
Contact Life @ load
100K ops (cosØ=1)
Operating Time
10ms max
Release Time
10ms max
VDR Rating (R1 to 4) 300Vac / 385Vdc
Maximum current pin 1 12Aac or dc (15A peak for <3s)
for UL: 10A @ max. 240Vac
(*) See Appendix 3 for UL508 ratings.
Connector X03
pin 1
C-R1,2,3
R1,2 and 3 common
pin 2
NO-R1
R1 normally open
pin 3
NO-R2
R2 normally open
pin 4
NO-R3
R3 normally open
pin 5
NO-R4
R4 normally open
pin 6
C-R4
R4 common
Connector X02 (optional)
pin 1
NO-R5
R5 normally open
pin 2
C-R5
R5 common
pin 3
NO-R6
R6 normally open
pin 4
C-R6
R6 common
Page 19 of 35