The last two contact inputs can be used to indicate the status of a Positive Temperature
Coefficient thermistor (PTC). The characteristics of the inputs are according to IEC 34-11-2,
VDE 0660.
Do not apply an external voltage on the PTC inputs as this
will damage the unit.
The two PTC inputs can also be used for switching contact inputs. If used in this way
attention to the type of contract must be made as the closed circuit current is low and may
not penetrate oxidisation. Use with gold flashed contracts in enclosed or sealed devices.
6.5 Relay outputs
The Airmaster R1 has 6 relays.
Switching Voltage (max) 240Vac (*) / 24Vdc
Continuous Current (max) 8Aac / 5Adc (resistive load) (**)
Breaking Capacity (max) 2000VA (cosØ=1) / 150W dc
Switching Rate
300 ops/min
Mechanical Life
10M ops
Contact Life @ load
100K ops (cosØ=1), 50K ops for 24VDC resistive (***)
Operating Time
10ms max
Release Time
10ms max
VDR Rating (R1 to 4) 300Vac / 385Vdc
Bridge Rating (continuous) 240Vac or dc / 8A
Maximum current pin 1 12Aac or dc (15A peak for <3s)
for UL: 10A @ max. 240Vac and 12A @ max. 150Vac
(*) relay 5 and 6: maximum 30Vac if normal closed contact are used.
(**) See Appendix 3 for UL508 ratings.
.
X02
R1
R2
R3
R4
R5
EXAMPLE
R6
K1
K2
K3
S1
LINK
1
14
+VC
0VC
R5
R6
Summary of Contents for Airmaster R1
Page 30: ...C M C n v Airmaster R1 installation guide base unit V1 1 MANY0317A 00 Page 30 of 41 ...
Page 31: ...C M C n v Airmaster R1 installation guide base unit V1 1 MANY0317A 00 Page 31 of 41 ...
Page 32: ...C M C n v Airmaster R1 installation guide base unit V1 1 MANY0317A 00 Page 32 of 41 ...
Page 33: ...C M C n v Airmaster R1 installation guide base unit V1 1 MANY0317A 00 Page 33 of 41 ...
Page 34: ...C M C n v Airmaster R1 installation guide base unit V1 1 MANY0317A 00 Page 34 of 41 ...