Operating instructions
3.3 Displaying maintenance reports
There are four maintenance reports available to help you
determine whether any fire alarm sensors require servicing. You
can view each report on the alphanumeric display.
Display a Dirty>80% report
Use the Dirty>80% command on the Maintenance menu to
display a Dirty>80% report. A Dirty>80% report lists all fire
alarm sensors whose compensation levels exceed 80%. The
compensation level value is an indication of a fire alarm sensor's
inability to compensate for environmental conditions.
Note:
Fire alarm sensors on this list require servicing as soon as
possible.
To display a Dirty>80% report:
1.
Press Menu.
2.
From the main menu, choose Reports, then Maintenance,
and then Dirty>80%.
3 Press Enter to accept the default (panel 01).
4. On the Report Output menu, choose the following:
•
Display to view the list on the alphanumeric display
Display a Dirty>20% report
Use the Dirty>20% on the Maintenance menu to display a
Dirty>20% report. A Dirty>20% report lists all fire alarm
sensors whose compensation levels exceed 20%. The
compensation level value is an indication of a fire alarm sensor's
inability to compensate for environmental conditions.
Note:
Fire alarm sensors on this list may require servicing and
should be watched carefully.
To display a Dirty>20% report:
1.
Press Menu.
2.
From the main menu, choose Reports, then Maintenance,
and then Dirty>20%.
3 Press Enter to accept the default (panel 01).
3.
On the Report Output menu, choose the following:
•
Display to view the list on the alphanumeric display