Clymac zm2 Operating And Maintenance Instructions Manual Download Page 20

Operating instructions

3.13 Switching event message routes

Event messages are programmed with a primary and an alternate
message route. Typically, a fire alarm system uses the primary
message route during daytime operation and the alternate
message route during night time operation.

In most applications, a time control is used to automatically
switch event messages over to their alternate route setting. When
the time control is restored, event messages are automatically
switched back to their primary route settings. You can override
the event message route in effect using the Alternate Message
Route command on the Activate menu and the Primary Message
Route command on the Restore menu.

Note: 

The default setting for both primary and alternate message

routes is "All Cabinets." When both event message route settings
are the same, switching message routes does not have any effect.

Switching from primary to alternate message routing

Use the Alt Msg Route (alternate message route) command on
the Activate menu to switch event message routing from primary
message routing to alternate message routing.

To switch from primary to alternate message routing:

1.

 

Log on using the level 2 password.

2.

 

From the main menu, choose Activate, then Alt Msg Route.

Switching from alternate to primary message routing

Use the Prm Msg Route (primary message route) command on
the Restore menu to switch event messages routing from
alternate message routing to primary message routing.

To switch from alternate to primary message routing:

1.

 

Log on using the level 2 password.

2.

 

From the main menu, choose Restore, then Prm Msg Route.

Summary of Contents for zm2

Page 1: ...aintenance reports 3 4 Displaying the alarm history 3 5 Performing a lamp test 3 6 Silencing the panel buzzer 3 7 Resetting the fire alarm system 3 8 Silencing sounders 3 9 Sounding an alarm 3 10 Disa...

Page 2: ...incident to be identified quickly reducing the search time and improving the chances of containing the incident 1 2 Analogue detection The ZM2 system utilises analogue detection techniques to detect f...

Page 3: ...s for future reference Weekly At weekly intervals a different fire detector or manual call point should be tested Any entry should be made in the log book quoting the particular trigger device that ha...

Page 4: ...e alarm system 3 2 Checking system status 3 3 Displaying or printing maintenance reports 3 4 Displaying the alarm history 3 5 Performing a lamp test 3 6 Silencing the panel buzzer 3 7 Resetting the fi...

Page 5: ...password lets you use the level 4 command menus Note The level 1 command menus do not require a password The control panel continues to let you use the command menus for the password you entered until...

Page 6: ...he Fire command on the Status menu to display a list of fire alarm points i e call point heat smoke verified smoke and sprinkler inputs that are not in the normal condition The list also includes any...

Page 7: ...put points Use the Outputs command on the Status menu to display a list of output points i e relay common alarm supervised audible and visible outputs that are not in the normal condition The list als...

Page 8: ...the Disabled Pts command on the Status menu to display a list of points that are disabled The list shows the device type address and the event message for each disabled point To display a list of disa...

Page 9: ...he main menu choose Reports then Maintenance and then Dirty 80 3 Press Enter to accept the default panel 01 4 On the Report Output menu choose the following Display to view the list on the alphanumeri...

Page 10: ...choose Reports then Maintenance and then Single Device 3 Enter the panel card device address PPCCDDD of the fire alarm sensor 4 On the Report Output menu choose the following Display to view the list...

Page 11: ...Reports menu to display the alarm history while the control panel is in an abnormal condition The alarm history display shows how many times the control panel has entered the fire alarm condition To d...

Page 12: ...urns on the panel buzzer all LED indicators and every pixel on the alphanumeric display Note When operated from the control panel CPU Display Unit the lamp test command only tests the control panel Wh...

Page 13: ...owledges all current event messages Unless programmed otherwise the panel buzzer automatically re sounds twenty four hours after being silenced provided that no new event messages are received at the...

Page 14: ...active condition If any inputs are still in a latched condition at the end of the reset cycle sounders if silenced will re sound and the panel buzzer if silenced will re sound Caution Do not reset th...

Page 15: ...silencing of fire alarm signals in which case the Silence Alarms switch may not be operational for up to five minutes after the initial fire alarm event Silenced outputs automatically re sound when Th...

Page 16: ...nd common alarm outputs Visible outputs are also activated unless programmed otherwise Pressing the Sound Alarms switch a second time returns these outputs to their normal condition To sound an alarm...

Page 17: ...group Use the Matrix command on the Disable Group menu to temporarily take a matrix group out of service and prevent it from initiating a set of responses To disable a matrix group 1 Log on using the...

Page 18: ...d on the Disable Group menu to temporarily take a time control out of service and prevent it from initiating a set of responses To disable a time control 1 Log on using the level 2 password 2 Choose D...

Page 19: ...ensitivity command on the Restore menu Note The default setting for both primary and alternate alarm sensitivity is Low When both alarm sensitivity settings are the same switching alarm sensitivity do...

Page 20: ...efault setting for both primary and alternate message routes is All Cabinets When both event message route settings are the same switching message routes does not have any effect Switching from primar...

Page 21: ...me and date The control panel includes a system clock that it uses to time stamp events and to activate time controls The time is presented in 24 hour format The date is presented in day month year fo...

Page 22: ...ommand on the Program menu to re initialise the fire alarm system without removing power To restart the fire alarm system 1 Log on using the level 2 password 2 From the main menu choose Program then R...

Reviews: