Clyde CKRS 05 Datasheet Download Page 5

Installation requirements

Fig 5 - Electricity supply

Electrical supply (Refer Fig 5)

230Vac 1ph burners are supplied as standard.  The fused
supply  should  be  taken  to  the  control  panel  only.    The
harness and connector supplied will feed the burner.

The  electricity  supplies  to  the  burner  and  boiler  control
panel must be wired in accordance with IEE Regulations.  A
separate  supply  and  isolating  switch  is  required  for  each
boiler in the plant room.

All  isolating  switches  and  fuses  must  be  provided  by  the
installer.  Burner start/run currents for fuse specification are
available on request.  Burner wiring diagrams and technical
data are also available on request.

All  connections  between  the  boiler  control  panel  and  the
burner  are  made  through  harnesses  with  matching  plugs
and sockets, supplied as standard.

Note:

Fig 5 is only diagrammatic.  Double pole switches with

the required minimum separation must always be used.

Air supply

Air for ventilation and combustion must be provided for
gas  fired  boilers  in  accordance  with  either  BS
6644:2011 or IGE/UP/10.  Air supply for oil fired boilers
must conform to BS 5410 : Part 2.

Chimney design

The  CKRS  boiler  is  designed  to  operate  with  a
pressurised combustion chamber and the chimney is
not required to assist the burner in overcoming the
boiler resistance.  The chimney must cater for the total
internal resistance of the flue system from each boiler
outlet  and  not  impose  an  additional  load  on  the
burner.

Water circulation (Refer Fig 4)

The flow water temperature from the boiler must reach
60°C (gas firing) or 50°C (oil firing) within 10 minutes
of the boiler being brought into operation.  Thereafter,
water circulation should be maintained through the
boiler such that the boiler flow water temperature is
always above 60°C (gas firing) or 50°C (oil firing).  A
pump  overrun  facility  is  necessary  to  ensure  that
water  circulation  is  maintained  for  at  least  three
minutes after the boiler is switched off.

There are several ways of providing boiler protection,
eg shunt pumps, primary loops, etc.  A typical boiler
pump and 3-port valve arrangement is shown in Fig
4a and b.

For multi-boiler systems a ‘reverse return’ pipework
configuration is required to ensure equal distribution
of water flow through the boilers.

Water treatment

Whenever a new boiler is connected to an existing
system, the pipework must be thoroughly cleaned and
flushed.  Carnot recommend that a permanent means
of filtration be fitted into the return pipework, such as a
sludge trap, hydrocyclone or full flow duplex filters.
The boiler guarantee will be invalid if waterways are
blocked by debris or carbonate deposits.  Long term
water treatment is essential to the economic operation
and life of both new and refurbished heating systems.

For  full  information  on  cleaning,  flushing  and
protecting  hot  water  systems,  refer  to  BSRIA
Application Guide  AG 1/2001.

T

T

T

Fig 4a Multiple boilers with individual pumps

Fig 4b Alternative arrangement for boiler protection with a primary
             loop

Boiler

Burner

loom

Isolator
& fuse

L

Control
panel

Burner

N

E

Single
phase
motor

EDS801/3 page5

Summary of Contents for CKRS 05

Page 1: ...tallation requirements 4 5 Boiler control wiring 6 7 Seasonal efficiency of over 84 gives compliance with ADL2B 2013 for gas fired boilers without the need for additional heating credits Compact heat...

Page 2: ...ating pressure of 6 bar and maximum temperature of 90oC CKRS boilers may be fired by Natural gas LPG Class D or Class C oil with 1 or 2 stage control The boiler is suitable for use in either open vent...

Page 3: ...cludes burner kg 289 334 381 429 474 Water volume litres 55 65 75 85 95 Flue gas mass flow 3 oxygen m h 8 4 10 4 12 3 14 2 16 2 Chimney draught Pa Gas side resistance mbar 1 65 1 82 2 05 2 3 2 55 Flue...

Page 4: ...ning the layout of the boiler room allowance must be made for opening the boiler door boiler assembling boiler cleaning and maintenance The boiler door may be hinged from the right as illustrated or t...

Page 5: ...e burner Water circulation Refer Fig 4 The flow water temperature from the boiler must reach 60 C gas firing or 50 C oil firing within 10 minutes of the boiler being brought into operation Thereafter...

Page 6: ...n Thermostat TR is a 1 stage item with CKCR1 and a dual thermostat 1 and 2 stage with CKCR2 0 I L1 L2 Fuse STB L3 L4 TR Thermometer EDS801 3 page6 Fig 6 Boiler control panel 1 2 3 4 5 6 7 8 9 10 11 12...

Page 7: ...eg timeclock L1 On off indicator lamp L2 Boiler high limit lock out lamp lamp is illuminated when running and goes out in lock out condition L3 Stage 1 run lamp L4 Stage 2 run lamp STB High limit ther...

Page 8: ...803 2 November 2014 Carnot Consult Ltd This publication is issued subject to alteration or withdrawal without notice The illustrations and specifications are not binding in detail All offers and sale...

Reviews: