M08R40A15-02
WSHN-XEE2 MF 10.2-120.2
9
4 Water connections
4.1 Water quality
Water features
•
confirming to local regulations
•
total hardness < 14°fr
•
within the limits indicated by table
The water quality must be checked by qualified personnel.
Water with inadequate characteristics can cause:
•
pressure drop increase
•
reduces energy efficiency
•
increased corrosion potential
Acceptable water quality values:
SO
4
2-
HCO
3
-
/SO
4
2-
Total Hardness
Cl
-
PO
4
3-
< 100
> 1
4,5 ÷8,5
< 50
< 2,0
NH3
< 0,5
PH
7,5 ÷9,0
ppm
dH
ppm
ppm
ppm
Fe
3
+
Mn
++
CO
2
H
2
S
Temperature
< 0,5
< 0,05
< 50
< 50
< 65
Oxygen content
< 0,1
Free Chlorine
< 0,5
ppm
ppm
ppb
°C
ppm
ppm
ppm
Provide a water treatment system if values fall outside the limits.
The warranty does not cover damages caused by limestone formations, deposits and impurities from the water supply and / or failure from
failed system clearing to clean system.
4.2 Risk of freezing
If the unit or the relative water connections are subject to temperatures close to 0°C:
•
mix water with glycol, or
•
safeguard the pipes with heating cables placed under the insulation, or
•
empty the system in cases of long non-use
4.3 Anti-freeze solution
The use of an anti-freeze solution results in an increase in pressure drop.
Make sure that the glycol type utilized is inhibited (not corrosive) and compatible with the water circuit components.
Do not use different glicol mixture (i.e. ethylene with propylene).
4.4 Water flow-rate
The project water-flow must be:
•
inside the exchanger operating limits (see the TECHNICAL INFORMATION section)
•
guarantee, also with variable system conditions (for example in systems where some circuits are bypassed in particular situations).
4.5 Hydraulic connections
•
take away the supplied connection union by acting on the connection joint
•
weld the union to the installation pipe
•
perform the connection between the installation pipe and the evaporator, using the joint
Do not weld the system pipe with the Victaulic connection joint attached.
The rubber gasket might be irreparably damaged.
Summary of Contents for WSHN-XEE2 MF 10.2
Page 13: ...M08R40A15 02 WSHN XEE2 MF 10 2 120 2 13 5 5 Connections performer by customer...
Page 46: ...46 WSHN XEE2 MF 10 2 120 2 M08R40A15 02 9 4 Source side 3 way modulating valve...
Page 47: ...M08R40A15 02 WSHN XEE2 MF 10 2 120 2 47 9 5 Source side 2 way modulating valve...
Page 48: ...48 WSHN XEE2 MF 10 2 120 2 M08R40A15 02 9 6 VALVE FOR DOMESTIC HOT WATER...
Page 63: ...Page intentionally left blank...